WIRING

The transmitter has standard screw block connectors and easy wire access to facilitate wiring. It is 

recommended that shielded twisted pair wiring at least 22 AWG be used for all connections and that the 

device wires not be run in the same conduit with wiring used to supply inductive loads such as motors. 

Disconnect the power supply before making any connections to prevent electrical shock or equipment 

damage. Make all connections in accordance with national and local electrical codes. 

The device power (24 Vac/dc) is connected to the terminal marked PWR. This terminal is used for the 

positive dc voltage or the hot side of the ac voltage. The device is reverse voltage protected and as such 

will not operate if connected backwards. 

For voltage output signal types (3-wire) or for AC power supply operation (3-wire), the common of the 

power supply is connected to the terminal marked COM. Note that this device has a half-wave type 

power supply which means the power supply common is the same as the output signal common. 

Therefore, several devices may be connected to one power supply and the output signals all share the 

same signal common. Use caution when grounding the secondary of an ac transformer or when wiring 

multiple devices to ensure that the circuit ground point is the same on all devices and the controller. This 

terminal is not used for loop-powered 4-20 mA output type (2-wire). 

The analog output signal is available on the OUT terminal. This signal is jumper selectable for either a 

voltage output or a standard loop-powered 4-20 mA output signal type. The analog output signal is 

typically connected directly to the Building Automation System (B.A.S.) and used as a control parameter 

or for logging purposes. 

For voltage type output signal the device has a minimum load that it is able to drive, similarly for current 

type output signal the device has a maximum load that it is able to drive with a particular power supply 

voltage. Observe and follow these ratings in the Specification section or inaccurate reading may result.

Figure 5

Figure 6

Figure 7

Wiring for output signals and 24 Vac/Vdc power from controller

Analog Input
Common
24 Vdc/ac Power

Controller

OUT

COM

PWR

OUT

COM

PWR

Controller

Power Supply

Input

Common

Common

24 Vdc

OUT

COM

PWR

Controller

Input

Common

24 Vac

OUT

COM

PWR

Controller

Power Supply

Input

Common

Common

24 Vdc

1:

 ±

0-MAX

2:

 ZERO

3:

 mA

 VOLT

24 Vac Power Supply, 4-20 mA Output

24 Vdc Power Supply, 0-10 Vdc Output

Current

Voltage

24 Vdc Power Supply, 4-20 mA Output

Low

HI

±

0-Max

mA

VOLT

2 1 3

OUT CO

M

PWR

IN-GE-ELPXXXXS-01-03      11/19

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Содержание ELP-S

Страница 1: ...e tubing without kinking and to make the electrical connections avoid locations with severe vibrations or excessive moisture Drill a hole in the duct and insert so the probe point is facing into the air flow The enclosure has a standard opening for a 1 2 conduit and may be installed with either conduit and a conduit coupler or a cable gland type fitting See Figure 1 The two mounting holes will fac...

Страница 2: ...s to ensure that the circuit ground point is the same on all devices and the controller This terminal is not used for loop powered 4 20 mA output type 2 wire The analog output signal is available on the OUT terminal This signal is jumper selectable for either a voltage output or a standard loop powered 4 20 mA output signal type The analog output signal is typically connected directly to the Build...

Страница 3: ...ied by measuring the output signal For voltage output configuration measure the voltage between the OUT and COM terminals The voltmeter should read between 0 10 Vdc For current output configuration insert a mA meter in series with the OUT terminal The mA meter should read between 4 and 20 mA OPERATION If the unit is set to a unipolar range such as 0 2 wc then the pressure applied to the High port ...

Страница 4: ...0 10 Vdc 3 wire field selectable Output Drive Capabilities Current 400 ohms max 24 Vdc Voltage 10K ohms min Zero Adjustments Push button auto zero Wiring Connections Screw terminal block 14 to 22 AWG Pressure Connection Barbed ports for 5 mm 0 170 ID flexible tubing Conduit Connection 1 2 NPT conduit or cable gland Enclosure Polycarbonate UL94 V0 IP65 NEMA 4X F style includes thread adapter 1 2 NP...

Отзывы: