Greystone Energy Systems ELP-S Скачать руководство пользователя страница 3

Page  3

CONFIGURATION

The transmitter is configured with jumpers located on the circuit board as shown on the PCB drawing in 

Figure 5. These jumpers are used to select the output signal type and the bipolar range/unipolar range (± 

or 0-MAX). 

The unit is factory configured to operate in the 4-20 mA output mode. To change to 0-10 Vdc out put 

move the jumper to the VOLT position as shown in Figure 6. 

The unit is factory set to unipolar.  To change to bipolar move the jumper to the +/- position as shown in 

Figure 7.

For example, if the model is for 2"wc and is the jumper labeled (±) is also selected, then the pressure 

range will be -2 to +2"wc. This means that each model has two pressure ranges, a bipolar range (±), and a 

unipolar range, 0-MAX.

PNEUMATIC CONNECTIONS

The one pressure port on the side of the enclosure is labeled Low. The static probe is the High port. This 

output signal reads a positive value when the port pressure is higher on the High port than the Low port. 

Use 0.170"I.D. flexible tubing for the pressure connections. Arrange the tubing to minimize the stress on 

the connections and ensure there are no kinks in the tubing.

Ensure the tubing to be used is clean and do not allow material to fall into the pressure ports as 

contamination could damage the sensor. When removing tubing use care to avoid breaking the ports. In 

some cases it is better to cut the tubing off rather that pulling it off but be careful not to cut the fitting or 

an air leak may occur.

POWER UP INSTRUCTION

Before turning on the power, verify all wiring to ensure that it complies with one of the included wiring 

diagrams and verify that the output signal type is correctly selected with the jumpers. Also, review the 

specifications to ensure the power supply is correct and that the pressure is within the correct range. 

At this time, also inspect the internal pressure tubing that connects the sensor to the external ports to 

ensure that the tubing did not get kinked during shipping or installation.

Proper operation can be verified by measuring the output signal. For voltage output configuration, 

measure the voltage between the OUT and COM terminals. The voltmeter should read between 0-10 

Vdc. For current output configuration, insert a mA meter in series with the OUT terminal. The mA meter 

should read between 4 and 20 mA.

OPERATION

If the unit is set to a unipolar range such as 0-2” wc, then the pressure applied to the High port must be 

higher than the pressure applied to the Low port. In this case, if the Low port is left open to ambient 

pressure and the High port is used to measure a positive pressure, then the output pressure can be 

calculated as follows:

 

4-20 mA 

Pressure = [(Output current - 4 mA) / 16 mA] x Range

 

0-10 Vdc 

Pressure = (Output voltage / 10 V) x Range

In the case of 0-2” wc, 4 mA or 0 V = 0” wc and 20 mA or 10 V = 2” wc. Since the transmitter is linear, 1” wc 

would be 12 mA or 5 V. If the positive pressure connection is reversed then the transmitter will always 

output 4 mA or 0 V.

If the unit is set to a bipolar range such as ± 1” wc, then the pressure applied to the High port should be 

higher than the pressure applied to the Low port for a positive output response. In this case, differential 

pressure can be measured using both ports. If the High port has a positive pressure with respect to 

the Low port, then the output indicates a positive pressure. Negative pressure is indicated if the High 

pressure is less than the Low pressure. For bipolar ranges, the output pressure can be calculated as 

follows: 

 

4-20 mA 

Pressure = [(Output current - 4 mA) / 16 mA] x 2 x Range - Offset

 

0-10 Vdc 

Pressure = (Output voltage / 10 V) x 2 x Range - Offset

CALIBRATION

All pressure ranges are factory calibrated and no calibration is necessary. The user may adjust the zero 

point if desired when changing ranges for example. Make sure the unit is warmed up for at least 10 

minutes (1 hour is best) before making a zero adjustment. With both ports open to the ambient pressure, 

press and hold the ZERO button for at least 3 seconds.  Release the button after at least 3 seconds and 

the device will calculate and store the new zero point.

IN-GE-ELPXXXXS-01-03      11/19

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Содержание ELP-S

Страница 1: ...e tubing without kinking and to make the electrical connections avoid locations with severe vibrations or excessive moisture Drill a hole in the duct and insert so the probe point is facing into the air flow The enclosure has a standard opening for a 1 2 conduit and may be installed with either conduit and a conduit coupler or a cable gland type fitting See Figure 1 The two mounting holes will fac...

Страница 2: ...s to ensure that the circuit ground point is the same on all devices and the controller This terminal is not used for loop powered 4 20 mA output type 2 wire The analog output signal is available on the OUT terminal This signal is jumper selectable for either a voltage output or a standard loop powered 4 20 mA output signal type The analog output signal is typically connected directly to the Build...

Страница 3: ...ied by measuring the output signal For voltage output configuration measure the voltage between the OUT and COM terminals The voltmeter should read between 0 10 Vdc For current output configuration insert a mA meter in series with the OUT terminal The mA meter should read between 4 and 20 mA OPERATION If the unit is set to a unipolar range such as 0 2 wc then the pressure applied to the High port ...

Страница 4: ...0 10 Vdc 3 wire field selectable Output Drive Capabilities Current 400 ohms max 24 Vdc Voltage 10K ohms min Zero Adjustments Push button auto zero Wiring Connections Screw terminal block 14 to 22 AWG Pressure Connection Barbed ports for 5 mm 0 170 ID flexible tubing Conduit Connection 1 2 NPT conduit or cable gland Enclosure Polycarbonate UL94 V0 IP65 NEMA 4X F style includes thread adapter 1 2 NP...

Отзывы: