Page  4

ModBus

Stop 1

ModBus

CRC A001

ModBus

Del     MI

Calibrat

1000 PPM

Use the <UP> or <DOWN> keys to toggle the stop bits between 1 and 2 (for some 

configurations the value is fixed). Press the <SAVE> key to save.

Use <UP> or <DOWN> to set the CRC value to A001 (CRC-16 reverse), 1021 

(CITT), 8005 (CRC-16), or 8408 (CITT reverse), then <SAVE> the value.

Use the <UP> or <DOWN> keys to change the value from MI (minimum) to 

50, 100, 150, 200, 250, 300, or 350ms. Press the <SAVE> key to save the value. 

(minimum delay means just more than 3.5 character time delays, 4ms for 9600 

baud rate, for example).

This item is used for 1000 ppm gas calibration and is explained in the 

Calibration

 

section.

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

5. STOP BITS

6. CRC VALUE

7. DELAY

8. CALIBRATION

Only if Relay option Installed

Relay

Test OFF

Use the <UP> or <DOWN> keys to toggle the relay ON or OFF. Press the 

<MENU> key to turn the relay off and advance to the next item.

9. RELAY

BackLite

ENABLE

Use the <UP> or <DOWN> keys to enable or disable the LCD backlight. When 

enabled the backlight is always on, when disabled it never lights. Press the 

<SAVE> key to save the setting.

10. BACKLIGHT

Only if viewable LCD Installed

Setpoint

Mode %

Use the <UP> or <DOWN> keys to select the set-point mode. The default is % 

for 0-100% (10% steps).

This can be changed to one of the following selections:

 

for 0-100% setpoint (5 % steps)

 

%RH  for 30 to 70 %RH setpoint (1 %RH steps)

 

ppm  for 500 to 1500 ppm setpoint (50 pm steps)

 

°C1 

for 18 to 24°C setpoint (0.5°C steps)

 

°C2 

for 10 to 30°C setpoint (0.5°C steps)

 

°C3 

for 16 to 26°C setpoint (0.5°C steps)

 

°F1 

for 67 to 73°F setpoint (1°F steps)

 

°F2 

for 60 to 80°F setpoint (1°F steps)

11. SET-POINT

Only if Set-point Option Installed

<SAVE> 

Press to exit the menu and return to normal operation or <MENU> to repeat the

 menu.

IN-GE-CDD3B1XXXMOD-01-03      11/19 Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Содержание CDD3B1 Series

Страница 1: ...tor is exposed to vibrations or rapid temperature changes Thecoverishookedtothebaseatthetopedgeandmustberemovedfromthebottomedgefirst Useasmall Phillips screwdriver to loosen the security screw as shown in Figure 1 Complete removal of the screw is not required Use the screwdriver to carefully pry each bottom corner if necessary Tip the cover away from the base and sit it aside as shown in Figure 2...

Страница 2: ...tive loads such as contactors coils or motors A network segment is a single shielded wire loop run between several devices nodes in a daisy chain configuration The total segment length should be less than 4000 feet 1220 meters and the maximum number of nodes on one segment length is 64 Nodes are any device connected to the loop and include controllers but do not include the EOL terminators To inst...

Страница 3: ...itch_Reset Register SET UP MENU The menu has several items as shown below To enter the menu press and release the MENU key while in normal operation This will enter the Setup Menu pressing the MENU key a second time advances to the next menu item The UP and DOWN keys are used to make changes to program variables by scrolling through the available options When a value is changed use the SAVE key to...

Страница 4: ... if Relay option Installed Relay Test OFF Use the UP or DOWN keys to toggle the relay ON or OFF Press the MENU key to turn the relay off and advance to the next item 9 RELAY BackLite ENABLE Use the UP or DOWN keys to enable or disable the LCD backlight When enabled the backlight is always on when disabled it never lights Press the SAVE key to save the setting 10 BACKLIGHT Only if viewable LCD Inst...

Страница 5: ...0 ppm CO2 gas a tank pressure regulator with flow restrictor and the necessary tubing to connect to the device Note that because of the Automatic Calibration Mode and other technology incorporated into the CDD series only a single point 1000 ppm calibration is required to meet specified accuracy Turn the regulator on off knob fully off and attach it to the 1000 ppm CO2 gas bottle and firmly tighte...

Страница 6: ...acitive Accuracy 2 RH Range 0 100 RH non condensing Resolution 1 RH Hysteresis 3 RH Response Time 15 seconds typical Stability 1 2 RH typical 50 RH in 5 years OPTIONAL RELAY OUTPUT Contact Ratings Form A contact N O 2 Amps 140 Vac 2 Amps 30 Vdc Relay Trip Point Programmable 500 to 1500 ppm via Modbus Relay Hysteresis Programmable 25 to 200 ppm via Modbus GENERAL Power Supply 20 to 28 Vac dc non is...

Страница 7: ...trol system programmers who may need to add support to their systmes to communicate with the device Modbus setup guide download is available online MODBUS PROTOCOL https downloads greystoneenergy com SG SG CDD3B1XXXMOD pdf IN GE CDD3B1XXXMOD 01 03 11 19 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com ...

Отзывы: