background image

Page  5

MODBUS TROUBLE-SHOOTING

The CO2/RH/T device operates as a slave. It will not communicate unless a master is connected 

to the network and sends a request for information, then the slave will answer. If the device does 

not communicate properly, first check that the communication wires are not reversed. Then check 

the communication parameters in the menu in the following sequence: Slave address, baud rate, 

transmission mode, parity bit, stop bit, RTU mode CRC polynomial and slave response delay.

The factory default Modbus address is 01 and each device must have its unique address to communicate 

properly on the bus. Use the menu as described above to change the Slave address to a unique number 

for each unit.

The default Modbus baud rate is 9600. Use the menu to change the baud rate to the correct setting.

The default transmission mode is RTU. If this is incorrect, use the menu to change the transmission mode 

to ASCII.

The default Modbus parity is N for None. If this is not correct, use the menu to change the parity from 

None to Odd or Even.

The default stop bits is 1. Use the menu to change the stop bit setting to 2. For some configurations the 

value is fixed.

The default Modbus CRC value is A001. The menu can be used to change this setting. This only applies 

to RTU mode and has no effect in ASCII mode. It is the CRC polynomial setting and can be changed 

between A001, 1021, 8005 or 8408.

The default Modbus delay is minimum (0). This can be changed as described above. It is the slave 

response delay and can be set from minimum to 350ms. For example, the minimum delay means 3.5 

character time delays or 4ms for 9600 baud rate.

CALIBRATION

Calibration with gas requires a field calibration kit consisting of an LCD, a bottle of 1000 ppm CO2 gas, a 

tank pressure regulator with flow restrictor and the necessary tubing to connect to the device.

Note that because of the Automatic Calibration Mode and other technology incorporated into the CDD 

series, only a single point 1000 ppm calibration is required to meet specified accuracy.

Turn the regulator on/off knob fully off and attach it to the 1000 ppm CO2 gas bottle and firmly 

tighten it by hand. Remove the cover of the unit to be calibrated to expose the gas sensor chamber. 

The tubing from the gas bottle can be connected to either port on the chamber after the plastic cap is 

removed. Gently remove one cap and connect the tubing, note that strong shock or vibration can affect 

calibration.

Ensure the device has been operating normally for at least five minutes before applying gas. Slowly turn 

the valve knob on the regulator to let the gas begin flowing.

The regulator will restrict the flow rate to the specified 100 ml/min. After a brief period the gas will flow 

into the chamber and the CO2 reading on the LCD will begin to approach 1000 ppm. Wait 1 to 2 minutes 

until the CO2 reading stabilizes.

Enter the Setup menu and use the <MENU> key to advance to Calibrat 1000 PPM. Press and hold the 

<SAVE> key for 2 seconds and the display will change to Waiting Calibrat then to Waiting 5 minute to 

indicate that the process of reprogramming the internal calibration setting is taking place.

This calibration process takes about 5 minutes and the LCD will count down the minutes. Do not disturb 

the unit or the gas flow during this period. When calibration is complete the unit will display Calibrat 

Done. Press the <SAVE> key to return to normal operation and then the gas can be shut off.

Disconnect the tubing and replace the cap on the sensor chamber as calibration is complete.

IN-GE-CDD3B1XXXMOD-01-03      11/19 Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Содержание CDD3B1 Series

Страница 1: ...tor is exposed to vibrations or rapid temperature changes Thecoverishookedtothebaseatthetopedgeandmustberemovedfromthebottomedgefirst Useasmall Phillips screwdriver to loosen the security screw as shown in Figure 1 Complete removal of the screw is not required Use the screwdriver to carefully pry each bottom corner if necessary Tip the cover away from the base and sit it aside as shown in Figure 2...

Страница 2: ...tive loads such as contactors coils or motors A network segment is a single shielded wire loop run between several devices nodes in a daisy chain configuration The total segment length should be less than 4000 feet 1220 meters and the maximum number of nodes on one segment length is 64 Nodes are any device connected to the loop and include controllers but do not include the EOL terminators To inst...

Страница 3: ...itch_Reset Register SET UP MENU The menu has several items as shown below To enter the menu press and release the MENU key while in normal operation This will enter the Setup Menu pressing the MENU key a second time advances to the next menu item The UP and DOWN keys are used to make changes to program variables by scrolling through the available options When a value is changed use the SAVE key to...

Страница 4: ... if Relay option Installed Relay Test OFF Use the UP or DOWN keys to toggle the relay ON or OFF Press the MENU key to turn the relay off and advance to the next item 9 RELAY BackLite ENABLE Use the UP or DOWN keys to enable or disable the LCD backlight When enabled the backlight is always on when disabled it never lights Press the SAVE key to save the setting 10 BACKLIGHT Only if viewable LCD Inst...

Страница 5: ...0 ppm CO2 gas a tank pressure regulator with flow restrictor and the necessary tubing to connect to the device Note that because of the Automatic Calibration Mode and other technology incorporated into the CDD series only a single point 1000 ppm calibration is required to meet specified accuracy Turn the regulator on off knob fully off and attach it to the 1000 ppm CO2 gas bottle and firmly tighte...

Страница 6: ...acitive Accuracy 2 RH Range 0 100 RH non condensing Resolution 1 RH Hysteresis 3 RH Response Time 15 seconds typical Stability 1 2 RH typical 50 RH in 5 years OPTIONAL RELAY OUTPUT Contact Ratings Form A contact N O 2 Amps 140 Vac 2 Amps 30 Vdc Relay Trip Point Programmable 500 to 1500 ppm via Modbus Relay Hysteresis Programmable 25 to 200 ppm via Modbus GENERAL Power Supply 20 to 28 Vac dc non is...

Страница 7: ...trol system programmers who may need to add support to their systmes to communicate with the device Modbus setup guide download is available online MODBUS PROTOCOL https downloads greystoneenergy com SG SG CDD3B1XXXMOD pdf IN GE CDD3B1XXXMOD 01 03 11 19 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com ...

Отзывы: