![Greyline ISM 5.0 Скачать руководство пользователя страница 27](http://html.mh-extra.com/html/greyline/ism-5-0/ism-5-0_user-manual_2264645027.webp)
Page 25
Minimizing Electrical Noise
The most effective way to minimize the effects of electrical noise is to make sure that
the pipe, the fluid and the flow meter body are all connected to earth ground. This
accomplishes two important goals. First, it ensures that the pipe, fluid and flow meter
are all at the same electrical potential. Second, it ensures that this electrical potential is
the same as earth ground.
In order to be certain that the meter is properly connected to earth, the flow meter earth
cable should be run directly to a known earth connection. The length of this earth cable
should be as short as practically possible, preferably ≤25 feet in length. The table below
lists earth connections from best to worst. If necessary, a separate earth cable should be
connected to the metal pipe near the meter.
Earth Connections (stranded wire 14 - 18 AWG)
Best
Earth grounding rod driven into the ground to the depth of the water table.
Earth wire connected directly to the building electrical service panel.
Worst
Earth wire connection inside an electrical outlet near the meter.
Diagnosing Electrical Noise Problems
When diagnosing electrical noise problems, it is important to understand that one of four
possible conditions is likely to exist. They are as listed in the table below. In order to minimize
the effects of noise, it is helpful to understand which of the following conditions are present.
Earth Connection at
Flow Meter
Pipe / Fluid Earth
Connection
Expected
Noise
Level
Possible Remedies
Good earth connection
≤ 25 feet from flow meter
Pipe & fluid are
connected to earth
Low
None required
Good earth connection
≤ 25 feet from flow
meter
Pipe & fluid are not
connected to earth
Moderate
A separate earth connection can be
made directly to the metal pipe or to the
fluid. Non-metallic pipes may require
grounding rings installed upstream and
downstream of the meter location.
Poor earth connection
Pipe & fluid are
connected to earth
Moderate
Removing the earth connection at the
flow meter may reduce the noise level.
If this is a long wire run, break the
connection where the wire connects to
the cable coming out of the flow meter.
If noise level is still too high, locate a
better earth connection for the flow
meter.
Poor earth connection
Pipe & fluid are not
connected to earth
High
Locate a better earth connection for the
flow meter. If noise level is still too
high, locate a better earth connection
for the pipe or fluid.
IMPORTANT NOTE
Non-metallic pipes are more susceptible to electrical noise. Grounding rings installed upstream
and downstream of the meter location to reduce the electrical noise present in the pipe may
be required for proper operation. Refer to section 1.5.1 and section 3.1 of this manual for
additional information on the use of grounding rings.
i