Page 29
TTFM 1.0 Transit Time Flow Meter
COMMON QUESTIONS AND ANSWERS
The pipe vibrates. Will it affect the flow meter?
Common vibration frequencies are far lower than the sonic frequencies used by the Greyline flow meter,
and will not normally affect accuracy or performance. However, applications where very weak Transit
Time signal is present (when sensitivity is adjusted to maximum and signal strength is low), accuracy
may be affected by pipe vibration, or the flow meter may show readings under no-flow conditions.
Attempt to relocate the sensor on a pipe section where vibration is reduced, or arrange pipe mounting
brackets to reduce vibration at the sensor mounting location.
The flow meter must be installed in a high noise environment. Will this affect operation?
Greyline flow meters are designed to discriminate between environmental noise and the Transit Time
signal. High noise environments may affect the flow meter’s performance where low signal strength
and/or low flow velocities are being measured. Relocate the sensor in a quieter environment if possible.
Will pipe corrosion affect accuracy of the flow meter?
Yes. Rust, loose paint etc. must be removed from the outside of the pipe to provide a clean mounting
position when installing a Transit Time sensor. Severe corrosion/oxidation on the inside of the pipe may
prevent the Transit Time signal from penetrating into the flow. If the pipe cannot be cleaned, a spool
piece (PVC recommended) should be installed for sensor mounting.
What effect do pipe liners have on the flow meter?
The air gap between loose insertion liners and the pipe wall prevent the Transit Time signal from
entering the flow. Better results can be expected with bonded liners such as cement, epoxy or tar,
however an on site test is recommended to determine if the application is suitable for a Transit Time
flow meter.
Why is Transit Time recommended for clean liquids?
The Transit Time sensor transmits sound across the flow stream in order to measure sound velocity and
therefore requires a fluid medium that is relatively transparent to the acoustic signal. The Transit Time
system will not function when there is high volume of solids or aeration. As a guideline, Greyline
Transit Time flow meters are recommended for clean liquids with solids or bubbles content less than
2%. Most applications such as water, chemicals and oils will meet this minimum requirement.
Can the sensor be submerged in water?
Yes, for short periods of time or by accident, but it is not recommended for continuous operation. The
sensor is constructed to withstand submersion to 10 psi (0.7 Bar) without damage.
What is the purpose of the Signal Strength Display?
The primary function of the signal strength display is to assist as a feedback when mounting sensors.
Signal Strength can also be a useful diagnostics tool when troubleshooting problems with an installation.
A low signal strength (< 20%) will cause the TTFM to be more susceptible to environmental noise and
may indicate a problem with the installation or other qualitative issues.
Содержание TTFM 1.0
Страница 2: ...Note This page has been left blank intentionally ...
Страница 4: ...Page 4 TTFM 1 0 Transit Time Flow Meter SENSOR INSTALLATION ...
Страница 6: ...Page 6 TTFM 1 0 Transit Time Flow Meter CONNECTIONS ...
Страница 9: ...Page 9 TTFM 1 0 Transit Time Flow Meter CALIBRATION MENU ...
Страница 10: ...Page 10 TTFM 1 0 Transit Time Flow Meter ICONS ...
Страница 24: ...Page 24 TTFM 1 0 Transit Time Flow Meter SENSOR MOUNTING COUPLING RECOMMENDATIONS BAD GOOD ...
Страница 36: ...Page 36 TTFM 1 0 Transit Time Flow Meter SENSOR INTRINSIC SAFETY ...