Page 14

PDFM 5.1 Portable Doppler Flow Meter

SENSOR MOUNTING LOCATION

The position of the sensor is one of the most important considerations for accurate Doppler flow
measurement. The same location guidelines apply to Doppler as most other types of flow meters.

Before permanently mounting a Doppler sensor onsite testing is recommended to determine optimum
mounting position. Use the sensor coupling compound (supplied with each Greyline flow meter, or
petroleum gel, acoustic compound or electrocardiograph gel). Take several readings around the axis of
the pipe and then at several points upstream and downstream from the selected position, checking for
consistent readings. Avoid high or low reading areas. Mount the sensor where consistent (average)
readings were obtained or continue testing on another pipe section.

VERTICAL OR HORIZONTAL PIPE - Vertical pipe
runs generally provide evenly distributed flow. On
Horizontal pipes and liquids with high concentrations
of gas or solids, the sensor should be mounted on the
side (3 or 9 o’clock position) to avoid concentrations of
gas at the top of the pipe, or solids at the bottom. For
liquids with minimal gas bubbles (e.g. potable water)
the sensor should be mounted on the top of a horizontal
pipe (12 o’clock position) to obtain the best signal strength.

VELOCITY INCREASING DEVICES: Generally the sensor must be mounted away from flow
disturbances such as valves, pumps, orifice plates, venturis or pipe inlets and discharges which tend to
increase flow velocity. Velocity increasing devices often cause cavitation, or rapid release of gas
bubbles, and readings both up and downstream may show much higher velocity. As a guideline, mount
the sensor at least 20 diameters upstream or 30 diameters downstream from velocity increasing devices.

Required distance from a velocity increasing device will vary in applications depending on the flow
velocity and the characteristics of the liquid itself.

TURBULENCE INCREASING DEVICES: Elbows,
flanged connections and tees tend to introduce
desirable conditions of an evenly distributed flow
profile with some air or gases entrained in the flow.
Sensor mounting 6 pipe diameters upstream and 10
diameters downstream from these disturbances is
generally optimum.

The sensor is designed to mount longitudinally on a straight section of pipe. Do not attempt to mount it
on bends, elbows or fittings.

Содержание PDFM 5.1

Страница 1: ...USER S GUIDE Installation Operation Instructions Portable Doppler Flow Meter Model PDFM 5 1 Manual Series A 1 1 ...

Страница 2: ...Page 2 Note This page has been left blank intentionally ...

Страница 3: ...NE 22 PRODUCT RETURN PROCEDURE 22 FLOW METER DATA SHEET 23 LIMITED WARRANTY 24 SPECIFICATIONS 25 APPENDIX A CONVERSION TABLE 27 PIPE CHARTS 28 IMPORTANT NOTE This instrument is manufactured and calibrated to meet product specifications Please read this manual carefully before installation and operation Any unauthorized repairs or modifications may result in a suspension of the warranty If this pro...

Страница 4: ...ed The PDFM 5 1 will switch off automatically when the battery is fully discharged Full charge requires approximately 6 hours charging Sleep mode extends battery life for long term data logging Maximum log time is 18 days at 5 minute sample rate CONNECTIONS SENSOR Use type PSE4 supplied with 12 ft 4 m cable Optional 50 ft 15 m extension cable available 4 20mA Active only when powered by AC charger...

Страница 5: ...1 menu system Arrows show the four directions to leave a menu box Pressing a corresponding keypad arrow will move to the next item in the direction shown Move the cursor highlighted under numerals and increase or decrease numerals with the and keys To store calibration values permanently press the ...

Страница 6: ...Page 6 PDFM 5 1 Portable Doppler Flow Meter CALIBRATION MENU ...

Страница 7: ...r on the MAIN display if error messages are being generated by the instrument Press to return to the main display STATUS Press from the MAIN display to view instrument status Velocity will be displayed in ft sec or m sec Tot Displays the current totalizer reading Signal Cutoff Adjust the setting in percent to suppress flow readings at zero flow when fluid swirling or pipe vibration may cause the i...

Страница 8: ...splay PASSWORD The password a number from 0000 to 9999 prevents unauthorized access to the Calibration menu From the Main display press the key to get to Password Factory default password is 0000 and if it has not been changed press the to proceed to the Menu Selections screen If a password is required press to place the highlight under the first digit and or to set the number then to the second d...

Страница 9: ...c etc Press the to store your selection then the to the next menu item and to enter From Linear press the key and then the or to select your units of measurement Press the to store your selection Press the key to move the symbol to each subsequent menu item and the to save your selections Note the volume selection bbl denotes U S oil barrel Press or to return to the Menu Selections screen ...

Страница 10: ...e raised to any value less than the 20mA setting or lowered to any velocity or corresponding flow rate down to 40 ft sec 12 2 m sec Min Vel Press and enter a minimum velocity cutoff Forward and reverse velocities less than Min Vel will be forced to zero Pipe ID Place the highlight under the digits and then or to change the numbers and decimal point Pipe ID should be entered as the exact inside dia...

Страница 11: ...Press or to select the logging interval Press to store the setting Log Select Start then to start logger Select Stop then to stop logger Select Delete then to clear all previous logging sessions RETRIEVE LOG FILE Install Greyline Logger on your PC or laptop Refer to the Help menu in the program for detailed instructions Connect the PDFM 5 1 to the PC using the supplied USB cable Install the USB dr...

Страница 12: ...om the totalizer Select NO to totalize forward flow only and ignore reverse flow Flo Direction Select On to enable flow direction measurement Select Off to disable flow direction measurement Select Invert to invert the sense of the flow measurement Cal Constant Scales the velocity reading Factory value is close to 1 000 for a PSE4 A sensor Restore Defaults Select Yes and press to erase all user se...

Страница 13: ... output 4mA to the analog channel To simulate measurements between minimum and maximum set Test to Actual and then enter for the flow measurement The analog output will respond to the simulated value SLEEP MODE Logging in sleep mode requires a minimum sample time of 30 seconds Selecting sleep mode for 10 second sampling rate results in instrument always being awake CHARGING A flashing battery indi...

Страница 14: ...top of the pipe or solids at the bottom For liquids with minimal gas bubbles e g potable water the sensor should be mounted on the top of a horizontal pipe 12 o clock position to obtain the best signal strength VELOCITY INCREASING DEVICES Generally the sensor must be mounted away from flow disturbances such as valves pumps orifice plates venturis or pipe inlets and discharges which tend to increas...

Страница 15: ...e and rust The objective of site preparation is to eliminate any discontinuity between the sensor and the pipe wall which would prevent acoustical coupling A PC4 Sensor Mounting Kit is supplied with each Greyline flow meter It includes recommended coupling compound in a plastic applicator and a stainless steel mounting bracket with adjustable pipe straps ...

Страница 16: ...mporary mounting Apply silicon coupling compound 4 to the coloured face of the sensor A bead similar to toothpaste on a toothbrush is ideal Do not overtighten crush the sensor The sensor must be fixed securely to the pipe with coupling material between the sensor face and the pipe Sensor installation with excessive coupling compound can result in gaps or voids in the coupling and cause errors or l...

Страница 17: ...Page 17 PDFM 5 1 Portable Doppler Flow Meter SENSOR MOUNTING COUPLING RECOMMENDATIONS ...

Страница 18: ...l pipe METER READING WHEN THERE IS NO FLOW Vibration on pipe Adjust Status Signal Cutoff setting Install in another location Variable Speed Drive interference Follow Drive manufacturers wiring and Grounding instructions Relocate Flowmeter Sensor and wiring away from VSD Sensor connections incorrect Refer to Connections diagram METER READING ERRATIC Sensor mounted too close to valve pump or elbow C...

Страница 19: ... vertical pipe Nearby velocity increasing device pump valve orifice plate Relocate sensor 30 pipe diameters from velocity increasing device Variable Speed Drive interference Follow Drive manufacturers wiring and Grounding instructions Relocate Flowmeter Sensor and wiring away from VSD BATTERY CONDITIONING To restore or condition your PDFM 5 1 battery for best performance fully discharge the unit l...

Страница 20: ... PVC recommended should be installed for sensor mounting What effect do pipe liners have on the flow meter The air gap between loose insertion liners and the pipe wall prevent the Doppler signal from entering the flow Better results can be expected with bonded liners such as cement epoxy or tar however an on site test is recommended to determine if the application is suitable for a Doppler flow me...

Страница 21: ...al to the velocity of flow All Greyline timing counting circuits use crystal controlled frequency references to eliminate any drift in the processing circuitry ISO 9000 or similar quality management systems may require periodic and verifiable recalibration of flow meters PDFM 5 1 Doppler Flow Meters may be returned to Greyline for factory calibration and issue of a new NIST traceable certificate R...

Страница 22: ... or email to obtain an RMA number Returned Merchandise Authorization This ensures fast service and correct billing or credit When you contact Greyline please have the following information available 1 Model number Software Version 2 Serial number 3 Date of Purchase 4 Reason for return description of fault or modification required 5 Your name company name address and phone number 2 Clean the Sensor...

Страница 23: ...Page 23 PDFM 5 1 Portable Doppler Flow Meter FLOW METER DATA SHEET ...

Страница 24: ...long with a copy of your invoice This warranty does not cover damages due to improper installation or handling acts of nature or unauthorized service Modifications to or tampering with any part shall void this warranty This warranty does not cover any equipment used in connection with the product or consequential damages due to a defect in the product All implied warranties are limited to the dura...

Страница 25: ...or formatted flow reports including total average minimum maximum and times of occurrence PC Software Greyline Logger for Windows 98 or higher Retrieves displays and saves data log files Electronics Operating Temperature 10 to 140 F 23 to 60 C Electronics Enclosure Portable ABS enclosure Carry Case Rated IP67 with protective molded foam insert Accuracy 2 of full scale requires solids or bubbles mi...

Страница 26: ...ng Frequency 640 KHz Sensor Housing Stainless Steel Sensor Cable 12 ft 3 66 m shielded coaxial pair Submersion Rating Withstands accidental submersion pressure up to 10 psi 0 7 Bar Options Sensor Cable 50 ft 15 m sensor cable extension shielded with connectors Sensor Mounting Extra silicone coupling compound Additional stainless steel pipe clamps Carrying Case Watertight carrying case with foam in...

Страница 27: ...ALLONS IMPERIAL GALS 0 8327 US GALLONS LITRES 3 785 US GALLONS CUBIC METERS 0 003785 LITRES SEC GPM 15 85 LITRES CUBIC METERS 0 001 BARRELS US GALLONS 42 BARRELS IMPERIAL GALS 34 9726 BARRELS LITRES 158 9886 INCHES MM 25 4 DEGREES F DEGREES C F 32 x 0 556 POUNDS KILOGRAMS 0 453 PSI BAR 0 0676 FOOT METER 0 0929 Note BARRELS are U S oil barrels ...

Страница 28: ...12 34 0 46 12 28 0 49 12 22 14 15 30 0 33 14 64 0 36 14 58 0 39 14 52 0 42 14 46 0 45 14 40 0 48 14 34 0 51 14 28 16 17 40 0 34 16 72 0 37 16 66 0 40 16 60 0 43 16 54 0 46 16 48 0 49 16 42 0 52 16 36 18 19 50 0 35 18 80 0 38 18 74 0 41 18 68 0 44 18 62 0 47 18 56 0 50 18 50 0 53 18 44 1875 375 20 21 60 0 36 20 88 0 39 20 82 0 42 20 76 0 45 20 70 0 48 20 64 0 51 20 58 0 54 20 52 24 25 80 0 38 25 04...

Страница 29: ... 564 218 24 24 000 23 563 218 23 500 250 Pipe Pipe Schedule 60 Schedule 80 Schedule 100 Schedule 120 Schedule 140 Schedule 160 Size O D I D WALL I D WALL I D WALL I D WALL I D WALL I D WALL 840 546 147 466 187 1 050 742 154 614 218 1 1 315 957 179 815 250 1 1 660 1 278 191 1 160 250 1 1 900 1 500 200 1 338 281 2 2 375 1 939 218 1 689 343 2 2 875 2 323 276 2 125 375 3 3 500 2 900 300 2 624 438 3 4 ...

Страница 30: ...0 16 11 40 0 68 10 04 12 13 20 0 54 12 12 13 20 0 62 11 96 13 50 0 68 12 14 13 50 0 75 12 00 14 15 30 0 57 14 16 15 30 0 66 13 98 15 65 0 74 14 17 15 65 0 82 14 01 16 17 40 0 60 16 20 17 40 0 70 16 00 17 80 0 80 16 20 17 80 0 89 16 02 18 19 50 0 64 18 22 19 50 0 75 18 00 19 92 0 87 18 18 19 92 0 96 18 00 20 21 60 0 67 20 26 21 60 0 80 20 00 22 06 0 92 20 22 22 06 1 03 20 00 24 25 80 0 76 24 28 25 ...

Страница 31: ......

Отзывы: