4mA CALIBRATION
20mA CALIBRATION
Wait for
4 =
and press
È
to display
20 =.
Now follow the same procedure to calibrate the distance from
the Sensor for 20mA output.
Remember that the LIT25 automatically reads LEVEL if
20 =
is set to the
minimum
distance from the
sensor. Calibrate in RANGE mode by setting
20=
to the
maximum
distance from the sensor.
Page 9
LIT25 Level Indicating Transmitter
Manual Series 3.5.1
È
20 =
È
È
È
761.9
761.8
761.7
Ç
Ç
Ç
762.1
762.2
762.3
The Display will alternate between
every 3 seconds.
MAXIMUM VALUES: 600 inches / 1524 cm
MINIMUM VALUES: 8 inches / 20.3 cm
MINIMUM SPAN (distance between 4= and 20=): 2" (5 cm)
and
RANGE
(Outage)
4mA =
20mA =
12"/30.5cm
2"/5cm
LEVEL
(Inventory)
20mA =
4mA =
12"/30.5cm
2"/5cm