ENCLOSURE INSTALLATION
Locate the enclosure within 500 ft (150 m) of the sensor. It can be wall mounted with four mounting
screws (supplied) or panel mounted with Option PM Panel Mounting Kit from Greyline Instruments.
Avoid mounting the enclosure in direct sunlight to protect the electronics from damage due to
overheating and condensation. Seal conduit entries to prevent moisture from entering enclosure.
NEMA4X (IP66) WITH CLEAR COVER
1. Remove enclosure cover.
2. Insert #6 screws through the four enclosure mounting holes
to secure enclosure to wall or mounting stand.
3. Replace Cover
An additional conduit hole can be cut in the end of the enclosure
if required. Use a screwdriver to "knock out" additional holes.
Note:
1. This non-metallic enclosure does not automatically provide grounding between conduit connections.
Grounding must be provided as part of the installation. Ground in accordance with the requirements of
the National Electrical Code. System grounding is provided by connecting grounding wires from all
conduit entries to the steel mounting plate or another point which provides continuity.
2. Water tight “O” ring seals must be used if cable strain-reliefs are used.
Page 14
LIT25 Level Indicating Transmitter
Manual Series 3.5.1
END VIEW
ENCLOSURE
MOUNTING
HOLES
ENCLOSURE
COVER