SENSOR MOUNTING/LOCATION
- Tank Level/Inventory Applications
Each LIT25 Level Transmitter includes a
non-contacting ultrasonic sensor. The sensor must be
installed in a position to obtain unobstructed echoes
from the liquid or material being measured.
Mount the sensor away from pipes, ladders, or
structural members which might cause continuous false
echoes.
Page 17
LIT25 Level Indicating Transmitter
Manual Series 3.5.1
SENSOR MOUNTED
AWAY FROM MATERIAL
PATH. COARSE SOLIDS
WILL USUALLY RETURN
AN ECHO EVEN IF AT
AN ANGLE
FINE POWDERS
MAY NEED SENSOR
TILTED NORMAL TO
SURFACE TO OBTAIN
GOOD ECHOES
SOLIDS AND POWDERS
90°
BAD
GOOD