E33.0.31.6C-02     

Manual for connection and operation of the GIR230 Pt1000 / DIF and GIR230 NTC /DIF

          Page 7 of 14

4.2. Selection of the output function

- The Display now shows “

outP

“. (output)

- Use button 2 and button 3 (middle and right button) to select the desired output-function.

The following table shows how the outputs will be configured on your selection.

Description

To select as

output

Output 1

(Relay 1)

Output 2

(Relay 2)

Output 3

(out 3)

See

chapter

No output, device is
used as display device

no

off

off

off

--

2-point-controller

2P

Switch-function 1

Switch-function 1,

inverted

Switch-function 1

5.1

3- point-controller

3P

Switch-function 1

Switch-function 2

Switch-function 1

5.1

2- point-controller with
min-/max-alarm

2P.AL

Switch-function 1

Min-/Max-alarm,

inverted

Min-/Max-alarm,

inverted

5.2

3- point-controller with
min-/max-alarm

3P.AL

Switch-function 1

Switch-function 2

Min-/Max-alarm,

inverted

5.2

min-/max-alarm

AL

Max-alarm,

inverted

Min-alarm,

inverted

Min-/Max-alarm,

inverted

5.3

- Press button 1 to validate the selected output function. The display shows “

outP

“ again.

When selected ‘no‘ as desired output you finished configuring your device. Press button 1 to switch over to
display the measuring value.

When selected a different output you have to configure the preferred states and delay time of the outputs
and the switch and alarm points.

Depending on your output function setting, it may be possible that one or more settings described below
won’t be available.

- When pressing button 1 again, the device will display “

1.dEL

“ (delay of switch function 1).

- Use button 2 and button 3 to set the desired value for switch function 1.

  Hint: The selected value [0.01 ... 2.00] will be in seconds.

- Press button 1 to validate the selection. The display shows “

1.dEL

“ again.

- Press button 1 again, the device will display “

1.Err

“ (error = preferred state of switch function 1).

- Use button 2 and button 3 (middle and right button) to set the desired output state in case of an error.

Display

Preferred state of the output

Note

off

Inactive in case of an error

on

Active in case of an error

- Press button 1 to validate the selection. The display shows “

1.Err

“ again.

- In case you selected a 3-point-controller you have to make the following settings similar to the settings

you already made for output 1:

2.dEL

“ (delay of output 2), “

2.Err

“ (preferred state of output 2).

Now you finished configuring the output functions. Depending on the selected output function you have to
make the settings for switching and alarm points. See description in chapter „switchpoints and alarm-
boundaries“ for further information.

Hint:

The settings for the switching and alarm points can be made later in an extra menu (see chapter 5)

Содержание GIR 230 NTC / DIF

Страница 1: ...E33 0 31 6C 02 Manual for connection and operation of the GIR230 Pt1000 DIF and GIR230 NTC DIF Page 1 of 14 Manual for connection and operation of GIR 230 Pt1000 DIF GIR 230 NTC DIF Version 1 3...

Страница 2: ...relay outputs 5 3 4 2 Connection of output 3 NPN output switching to ground 5 4 CONFIGURATION OF THE DEVICE 6 4 1 Selecting an input signal type 6 4 2 Selection of the output function 7 5 SWITCHPOINT...

Страница 3: ...he device must be switched off and must be marked against re starting in case of obvious malfunctions of the device which are e g visible damage the device is not working as prescribed after storage o...

Страница 4: ...factory the GIR230 has been subjected to various inspection tests and is completely cali brated Before the GIR230 can be used it has to be configured for the customer s application Hint In order to av...

Страница 5: ...switching outputs properly Please take care that you must not exceed the limits of the voltage and of the maximum current of the switching outputs not even for a short period of time Please take extr...

Страница 6: ...the device switches to the lower limit vice versa 4 1 Selecting an input signal type Turn the device on and wait until it completed its built in segment test Press button 2 for 2 sec The display will...

Страница 7: ...you have to configure the preferred states and delay time of the outputs and the switch and alarm points Depending on your output function setting it may be possible that one or more settings describ...

Страница 8: ...ss button 1 when not already done The device will be displaying 1 on turn on point of output 1 Use button 2 and button 3 to set the desired value the device s output 1 should be turning on Press butto...

Страница 9: ...points for the second switching function 2 on 2 off Configuring these settings like the first switching function After that the alarm outputs have to be configured When pressing button 1 the device w...

Страница 10: ...stays above 50 C for the entered delay time or after it had been falling below 15 C and stays below 15 C for the entered delay time Please note that the alarm outputs are inverted This means that the...

Страница 11: ...1 slope adjustment 1 100 Example The setting is 2 00 the slope has risen 2 00 slope 102 When measuring a value of 1000 without slope adjustment the device would display 1020 with slope adjustment of 1...

Страница 12: ...s check probe and device configuration Err 7 System error The device features an integrated self diagnostic function which checks essential parts of the de vice permanently When detecting a failure er...

Страница 13: ...ty 5A 230VAC resistive load NPN output NPN Open Collector breaking capacity 30mA max 28VDC Output functions 2 point 3 point 2 point with alarm 3 point with alarm min max alarm Switching points arbitra...

Страница 14: ...E33 0 31 6C 02 Manual for connection and operation of the GIR230 Pt1000 DIF and GIR230 NTC DIF Page 14 of 14...

Отзывы: