GIR1002 FR / GIA1000 FR Connecting and Operating Manual Version: 4.03-3 page: 6
Operation
Start-up
As soon as the supply voltage has been applied the GIR1002 FR will carry out a ssystem test for
approx. 8s. Then the current measuring value will be displayed.
Table of Functions
The various functions are called up/input by means of the 4 buttons located at the front side of the
device. We would like to point out that depending on the output configuration (also refer to chapter
‘
configuration
’
) only a certain number of functions will be available.
The following table shows all the functions of the GIR1002 FR. The right hand column
indicates the controller configuration for the various functions.
Output
Functions
To be called up by
configuration
-------------------------------------------------------------------------------------------------------------------------------------
display of current measuring value:
briefly pressing button 4
0 .. 8
set tara function:
briefly pressing button 4
optional
alarm reset:
pressing button 4 for 4 s
2,3,5,6
tara function reset:
pressing button 4 for 4 s
optional
display of max. value:
briefly pressing button 2
0 .. 8
max. value reset:
pressing button 2 for 4 s
0 .. 8
display of min. value:
briefly pressing button 3
0 .. 8
min. value reset:
pressing button 3 for 4 s
0 .. 8
Switching point output 1
display/setting of making point:
button 1 .. 4
1,2,3,7
display/setting of switching point:
button 1 .. 4
4,5,6,8
display/setting of breaking point:
button 1 .. 4
1,2,3,7
display/setting of hysteresis:
button 1 .. 4
4,5,6,8
Switching point output 2
display/setting of making point:
button 1 .. 4
1
display/setting of switching point:
button 1 .. 4
8
display/setting of breaking point:
button 1 .. 4
1
display/setting of hysteresis:
button 1 .. 4
8
Alarm
display/setting of max. alarm limit:
button 1 .. 4
2,3,5,6
display/setting of min. alarm limit:
button 1 .. 4
2,3,5,6
display/setting of alarm delay:
button 1 .. 4
optional
(2,3,5,6)
Display of current measuring value or acitvate tara function
To be called up by:
briefly pressing button 4
Note:
If the controller is set to the function
“
display of max. value
“
respectively
“
display of min. value
“
, pressing of button 4 will result in the display
switching over to show the current measuring value. If the current
measuring value is already on display, pressing of button 4 results in a
reset of the tara function.
Display:
the current measuring value is shown on the 7-segment display
LED
“
1
”
:
gives status of relay 1
LED
“
2
”
:
gives status of relay 2
LED flashing: relay contact made
LED not flashing: relay contact broken
LED
“
ALARM
”
:
LED flashing in case of alarm.
LED
“
min
”
:
LED flashing in case of MIN alarm.
LED
“
max.
”
:
LED flashing in case of MAX alarm.
LED
“
CAL
”
:
LED flashing in case of tara function being active