GIR1002 FR / GIA1000 FR Connecting and Operating Manual Version: 4.03-3 page: 10
5) LED
“
CAL
“
is illuminated.
The display will show
“
FIL.0
“
,
“
FIL.1
“
,
“
FIL.2
“
or
“
FIL.3
“
.
Use buttons 2 and 3 to select filter desired (point will start flashing).
“
FIL.0
“
:
no filter
“
FIL.1
“
:
filter 1 active
“
FIL.2
“
:
filter 2 active
“
FIL.3
“
:
filter 1 and filter 2 active
Filter1:
for filtering short pikes occurring when relays and contactors are switched. Make sure to
always activate filter 1 if high loads are switched in the vicinity of the controller, wires or sensor or if
large pikes are to be expected.
Additional display delay: approx. 0.5s
Filter 2:
prevents
“
jumping
“
of the last figure, a phenomenon often found with digital displays and
controllers. Make sure to always activate filter 2 if the display range exceeds 2000 digits.
Additional display delay: approx. 1s
Acknowledge filter selected by pressing button 4
6) LED
“
CAL
“
is illuminated.
The display shows the letter combination
“
nr.
“
followed by the interface address set (0 .. 15).
Use buttons 2 and 3 to set new interface address (point will start flashing) and acknowledge by
pressing button 4.
If the RS485 interface is not used, this setting will not have any meaning (please also refer to
description of interface).
7) LEDs
“
Analog
“
,
“
max.
“
and LED
“
CAL
“
are illuminated.
The display will show the measuring value stored in the GIR1002 FR for which a 20mA signal will be
given at the analog output.
(This function is only available for devices equipped with the option
“
analog output
“
.)
Use buttons 2 and 3 to set new display value for an output current of 20mA (LED
“
max.
“
will start
flashing); acknowledge by pressing button 4.
8) LEDs
“
Analog
“
,
“
min.
“
and LED
“
CAL
“
are illuminated.
The display will show the measuring value stored in the GIR1002 FR for which a 4mA signal will be given
at the analog output.
(This function is only available for devices equipped with the option
“
analog output
“
.)
Use buttons 2 and 3 to set new display value for an output current of 4mA (LED
“
min.
“
will start flashing);
acknowledge by pressing button 4.
9) LED
“
CAL
“
is illuminated.
The display shows the letter combination
“
out.
“
followed by the controller type set (0 .. 8).
(
This function is not available for GIA1000 FR devices).
Use buttons 2 and 3 to set desired controller type (point will start flashing).
"out.0":
display only
“
out.1:
3-level controller
“
out.2
“
:
2-level controller with alarm, self-extinguishing
“
out.3
“
:
2-level controller with alarm, with hand-shake
“
out.4
“
:
2-level controller with hysteresis preselectable
“
out.5
“
:
2-level controller with hysteresis preselectable,and alarm with
interacting set-point value, self-extinguishing
"out.6":
2-level controller with hysteresis preselectable, and alarm
with interacting set-point value, with hand-shake
“
out.7
“
:
2-level controller
“
out.8
“
:
3-level controller with hysteresis preselectable
Acknowledge controller type selected by pressing button 4.
The display will show the current measuring value again.
The configuration of the GIR1002 FR has now been completed.
Steps 1 to 10 can be repeated any number of times to either correct a setting error or to input a new setting.
Unless a button is pressed at least approx. every 2 minutes during the setting process, the GIR1002FR
will stop the setting process. Then,
“
CAL
“
will stop flashing. In such a case we recommend to repeat the
setting process.