23
GF-A2100
AND
GF-A2200 A
IRFLOW
M
EASUREMENT
S
TATION
Air Flow Measurement, PID Control and Alarm Solution - Analog Output
GreenTrol Automation, Inc.
•
156 Holly View Lane Loris, SC 29569
•
Toll Free: 877-4GN-TROL (877.446.8765)
•
Internet:
GreenTrol.com
Setup Menu Options (Part 1 of 3)
(Refer to Table 2 for “SI” Standard International Units of Measure)
Figure 15. GF-A2100/GF-A2200 Setup Menu Option (“IP SYS”)
Press and release
↑
/
↓
during normal operation to select
* Factory Default/Current Setting
Enter (move
→
)
Enter (move
→
)
Enter (move
→
)
Enter (action, move
←←
)
Esc (normal oper.)
Esc (move
←
)
Esc (move
←
)
Esc (move
←←
)
ACTION
isible only when
SYS CFG = DUAL
isible only when
SYS CFG = DUAL
isible only when
OFF-GAIN1=ON
SYS CFG=DUAL
↑
*AR2=0.00 S F
Ľ
SET AR2?
AR2=0.00 S F
↑
AR1=0.00 S F
↑
OFF-GAIN1=ON
↑
*OFF-GAIN1=OFF
Ľ
SET OFF-GAIN1?
OFF-GAIN1=OFF
↓
*ALT=0
↑↓
Set area 2 between 0.00 and
.
sq.ft. Area affects the LCD display
reading and output.
*FILTER2= 0
Ľ
AD UST FILTER2?
FILTER2=0
↑
Ad ust dampening filter value from 0 (off) to
%.
Offset/Gain ad ustments and menus for Airflow 1 Output are enabled
*SYS CFG=A G
Ľ
SET SYS CONFIG?
SYS CFG=A G
↓
Set the system to average readings from the connected probes.
Ad ust dampening filter value from 0 (off) to
%.
IP/SI=IP SYS
↓
SET AR1?
IP/SI=SI SYS
↑
SET SYSTEM?
*AR1=0.00 S F
Ľ
*INT TIM= 1S
Ľ
SET INT TIME?
*O-G MODE1=1
Ľ
SET O-G MODE1 ?
AD UST FILTER1?
Set system units to Inch-Pound units (FPM, CFM, sq.ft,
°
F)
SYSTEM SETUP
↓
*IP/SI=IP SYS
↓
Set system units to International System of Units (MPS, LPS, sq.M,
°
C)
*FLOW BUF= 10
Ľ
SET FLOW BUF ?
*FILTER1= 0
Ľ
INT TIME= 1.0S
↑
Set the amount of time between updating the flow (0.1-120s).
FILTER1=0
↑
BUFF SI E = 10
Ľ
Set the number of calculations used in the average (1-500).
O-G MODE1=1
↓
Mode 1 displays offset/gain values when ad usting output.
Set area 1 between 0.00 and
.
sq.ft. Area affects the LCD display
reading and output.
Set the system to process readings from the probes individually.
SET ALTITUDE?
*ALT=0FT
↑
Set the altitude for flow correction from 0 to 1 ,000 ft.
Offset/Gain ad ustments and menus for Airflow 1 Output are disabled
isible only when
OFF-GAIN1=ON
isible only when
OFF-GAIN1=ON
isible only when
SYS CFG = DUAL
isible only when
OFF-GAIN2=ON
isible only when
OFF-GAIN2=ON
isible only when
OFF-GAIN2=ON
TO PART 2
airflow u/m (+/-)
Ad ust
Ľ
while viewing airflow rate when O-G Mode 2 is selected. /-
indicates direction of ad ustment from initial value -
to
.
airflow u/m (+/-)
Ad ust
Ľ
while viewing airflow rate when O-G Mode 2 is selected. /-
indicates direction of ad ustment from initial value.
*OFFSET2= 0
↑
OFFSET2=0
Ľ
Ad ust
Ľ
to set offset when O-G Mode 1 is selected.
O-G MODE2=2
↑
Mode 2 displays airflow rate (real time) when ad usting output.
*GAIN2=1.000
Ľ
SET GAIN2?
Ad ust
Ľ
to set gain when O-G Mode 1 is selected .001 to
.
.
OFF-GAIN2=ON
↑
Offset/Gain ad ustments and menus for Airflow 2 Output are enabled
*O-G MODE2=1
Ľ
SET O-G MODE2 ?
O-G MODE2=1
↓
Mode 1 displays offset/gain values when ad usting output.
airflow u/m (+/-)
Ad ust
Ľ
while viewing airflow rate when O-G Mode 2 is selected. /-
indicates direction of ad ustment from initial value -
to
.
*OFF-GAIN2=OFF
Ľ
SET OFF-GAIN2?
OFF-GAIN2=OFF
↓
Offset/Gain ad ustments and menus for Airflow 2 Output are disabled
airflow u/m (+/-)
Ad ust
Ľ
while viewing airflow rate when O-G Mode 2 is selected. /-
indicates direction of ad ustment from initial value.
*OFFSET1= 0
Ľ
SET OFFSET1 ?
OFFSET1=0
Ľ
Ad ust
Ľ
to set offset when O-G Mode 1 is selected.
*GAIN1=1.000
Ľ
SET GAIN1?
O-G MODE1=2
↑
Mode 2 displays airflow rate (real time) when ad usting output.
GAIN2=1.000
Ľ
SET OFFSET2 ?
GAIN1=1.000
Ľ
Ad ust
Ľ
to set gain when O-G Mode 1 is selected .001 to
.
.
O