Greentrol Automation GF-A2100 Скачать руководство пользователя страница 14

Automation, Inc.

14

TM_GF-

A

2

1

00_2200_R1A

GF-A2100 

AND

GF-A2200 A

IRFLOW

M

EASUREMENT

S

TATION

Air Flow Measurement, PID Control and Alarm Solution - Analog Output

GreenTrol Automation, Inc.

•    

156 Holly View Lane  Loris, SC 29569    

•   

Toll Free: 877-4GN-TROL  (877.446.8765)   

•   

Internet: 

GreenTrol.com

Alarm Output Connections

The GF-A2100/GF-A2200 provides an alarm output that can be configured as relay dry contacts, or as direct drive (15
mA typical) for an external LED alarm indicator.   The alarm output interface is set using the LED PWR jumper on the main
circuit board as shown in Figure 9.  With the LED PWR jumper on, the alarm output is set to provide an external LED drive
(15 mA typical) at terminal 4, with ground return at terminal 6.  With the LED PWR jumper OFF, the alarm output is set
to provide relay dry contacts between terminals 4 and 5 (contacts rated at 30VDC/24VAC 3 amps maximum).  The Alarm
can be set as contacts close or contacts open on alarm as detailed in the Transmitter Setup menu later in this manual.

For external LED drive alarm output, ensure that the LED PWR jumper is installed, and connect the LED anode (+)

to terminal 4, and cathode (-) at terminal 6.  

OR

For relay dry contact alarm output, ensure that the LED PWR jumper is removed, and connect the alarm wires to

terminals 4 and 5. Contact rating is 30VDC/24VAC 3 amps maximum. 

Sensor Probe Connection

With 24VAC power OFF, connect each sensor probe cable plug to the transmitter by pushing it into the keyed cir-

cular receptacle (shown below) located at the bottom of the transmitter enclosure.  Do not twist the connector.

Sensor probe cable plugs are “keyed”.  Line up the connector plug with the transmitter receptacle and push straight on.  DO NOT
TWIST.  Squeeze cable plug “ribs” towards receptacle when removing.  Forcing the cable plug in or out of the receptacle will dam-
age the connectors and void warranty.

Sensor probe must be connected to the transmitter before application of 24VAC power in order to properly “flash” sensor calibra-
tion data to the transmitter.

Initial Power Up

Upon application of 24VAC power, the GF-A2100/GF-A2200 will initiate a brief self-test, indicated by dashed lines on the
LCD, and then will automatically engage the Start Up Menu to prompt the user through menus that configure the trans-
mitter for the specific installation/application.  The Start Up menu will also be engaged each time power is applied and
the required area for any of the connected probes has not been set (*AR1(and/or AR2)=0.00 SQF).  Refer to the Start
Up Menu and Set Up menu details and descriptions later in this manual for a complete description of programming
options and features.

Operating Modes

The GF-A2100/GF-A2200 provides two independent 12-bit (4096 discrete states) linear analog outputs.  Each output
can be independently enabled, disabled and configured within the Set Up Menu as follows:

Set as Standard flow or Temperature output from Flow 1 (and Flow 2) probes.
Set as a PID Control output signal (with advanced PID control options available)
Set as an airflow alarm status output (to indicate Hi limit, Low limit or Deadband with hysteresis conditions)
Set as a temperature alarm output (to indicate Hi limit, Low limit or Deadband with hysteresis conditions)
Set as Differential flow output to indicate the difference between Flow 1 and Flow 2 probes (GF-A2200 only)

In addition, the text displayed for each output on the GF-A2100/GF-A2200 LCD display panel can be renamed to suit your
specific requirements (5 characters max).  Analog outputs are field selectable for 0-10VDC, 0-5VDC or 2-10VDC to per-
mit simple integration with virtually all building automation systems.  Refer to the Set up menu details and descriptions
later in this manual for a complete description of analog output and PID control output options.

Push/Pull to Connect/Disconnect

DO NOT TWIST!

Keyway

Содержание GF-A2100

Страница 1: ...Analog Output Part Number 960 0220 Automation Inc Greentrol Automation Inc Installation Operation and Maintenance Technical Manual GF A2100 GF A2200 Dual Analog Output Air Flow Measurement with PID C...

Страница 2: ...Free 877 4GN TROL 877 446 8765 Internet GreenTrol com LIST OF EFFECTIVE AND CHANGED PAGES Insert latest changed pages i in bold text remove and dispose of superseded pages Total number of pages in thi...

Страница 3: ...ALR SRC 16 Alarm Type ALR TYP 16 Converting Analog Output Signal Values for Airflow and Temperature 17 Sending a Test Output Signal to the Host Control System 17 GF A2100 GF A2200 TRANSMITTER SET UP 1...

Страница 4: ...Economizer Hood and Duct Applications 10 Figure 7 GF A2200 Two Probe Insertion Mount Detail for Economizer Hood and Duct Applications 11 Figure 8 GF A2100 GF A2200 Transmitter Mechanical Detail Drawi...

Страница 5: ...a process low limit can be set to force the output to zero when the airflow rate falls below a low limit Both features are beneficial on outside air intakes affected by transient wind gusts at low air...

Страница 6: ...is of sufficient length to reach the planned transmitter installation site It is recommended that the probe be installed first to ensure that the included cable will reach the transmitter after allow...

Страница 7: ...Drill holes suitable for the hardware that will be used to secure the bracket at two locations 4 Carefully align the bracket mounting holes with the holes prepared in the previous step 5 Secure each...

Страница 8: ...two probe Unit Ventilator Application Universal Mount Probe Applications 2 UPSTREAM OF OA DAMPER BLADE EDGE AT 100 OPEN X LEFT SENSOR CENTER LOCATION PLANE OF THE EDGE OF OA DAMPER BLADES AT 100 OPEN...

Страница 9: ...00 at the location s marked in step 1 using a 0 875 inches 22 2 mm hole saw 4 Temporarily slide the probe and bracket through the hole prepared in step 3 so that the airflow label on the brack et is p...

Страница 10: ...UIDE SCORE LINE AT NOTCH ON BLOCK SECURE PROBE SET SCREW PREPARE AN INSERTION MARK ACROSS FACTORY GUIDE MARK AT 3 X D WALL INSULATION inches 76 2 X D WALL INSULATION mm MEASURED FROM THE NON CABLED EN...

Страница 11: ...X D WALL INSULATION inches 76 2 X D WALL INSULATION mm MEASURED FROM THE NON CABLED END OF PROBE PROBE INSERTION FACTORY GUIDE SCORE LINE SENSOR CENTER LINE PROBE ALIGNMENT SET SCREW NYLON BLOCK Note...

Страница 12: ...e engineer s plans locate where the transmitter will be installed 2 Refer to Figure 8 and mark the two mounting holes located on each of the side flanges of the transmitter 3 Drill two holes suitable...

Страница 13: ...GF A2100 GF A2200 The GF A2100 GF A2200 is a non isolated device with a half wave rectifier on the 24VAC power input terminal at pin 7 Therefore to prevent equipment damage multiple devices that are...

Страница 14: ...ll dam age the connectors and void warranty Sensor probe must be connected to the transmitter before application of 24VAC power in order to properly flash sensor calibra tion data to the transmitter I...

Страница 15: ...ACTS 30VDC 24VAC 3 AMPS MAX ALARM RELAY DRY CONTACT VALID ONLY WHEN LED PWR JUMPER IS REMOVED COM EXTERNAL LED ALARM INDICATOR EXTERNAL ALARM LED 15 mA ILLUMINATES ON ALARM LED PWR JUMPER INSTALLED AL...

Страница 16: ...Setup menu refer to Setup Menu detail later in this document ALR TYP DEADB Sets alarm as Deadband type where measurement outside of a range defined by the setpoint value A ASP plus or minus the hyster...

Страница 17: ...Analog Output 2 x FS MS x 0 125 MS NOTES 1 Setup menu for flow measurement OUT TYPE FLOW 2 Setup menu for temperature measurement OUT TYPE DIFF 4 FS is the full scale analog output value in the Setup...

Страница 18: ...flow measurement configuration either averaged reading for single or dual probe models or independent readings for dual probe models and the free area measurement where probes are located Additional f...

Страница 19: ...per Esc move Esc move Esc move ACTION Custom LCD Flow Text Blinking prompt shows position of the selected character Up and down arrows select between available characters ENTER accepts current charact...

Страница 20: ...en using the ENTER button navigate into the SYSTEM SETUP menu to the System of Units sub menu as shown in Figure 13 Press ENTER to proceed to the right three times and then use the UP and DOWN arrow b...

Страница 21: ...rm activation 15 15 ADEL Alarm Delay sets the time period that the Alarm condition must be present before the Alarm is activated 5S 5S ALRM POL Alarm relay contact configuration NO for normally open o...

Страница 22: ...essing and releasing the UP and DOWN buttons while the transmitter is in its normal operating mode see Figure 15 for detailed flow chart of the Setup menu Changes made in the Setup menu take effect im...

Страница 23: ...500 O G MODE1 1 Mode 1 displays offset gain values when ad usting output Set area 1 between 0 00 and sq ft Area affects the LCD display reading and output Set the system to process readings from the...

Страница 24: ...ivated SET ALRM POL SET ALRM YS ALR SRC OFF ALR TYP DEADB ALR TYP I ALR TYP LO ALRM POL NO ALRM YS 15 ALRM POL NO Alarm source is related to FLOW2 Alarm source is related to TEMP2 Alarm source is rela...

Страница 25: ...ed to control the value of FLOW1 Control loop is used to control the value of FLOW2 Control loop is used to control the difference between FLOW1 and FLOW2 ACTION RE ERSE DI ISR 1000 SET DI ISR DEADB 1...

Страница 26: ...plifies con trol and interpretation of the airflow rate signal on many applications To set the low limit cutoff enter Setup menu and set LL desired value as shown in Figure 15 Adjusting the Digital Ou...

Страница 27: ...TO DESIRED SPEED FLOW1 0 Set to 0 999999cfm using Wait Field Cal Done AUTO FS 100 Change FS NO During the 2 minute Wait period the Field Calibration Wizard acquires 1200 samples of the airflow rate a...

Страница 28: ...nd intervals The sensor detection system has detected a malfunc tioning or missing sensor Check sensor probe cable connection If connection is OK contact customer service for further assistance Wrong...

Отзывы: