6. BALANCING THE UNIT WITH THE DUOTROL™ SYSTEM (LCH-4E & LCH-7E ONLY)

The light indicator shows you in which mode the  

Duotrol

TM

 System is in.

  

GREEN LIGHT Mode Selector

  

YELLOW LIGHT Balancing Mode

USING THE SELECTOR SWITCH 
NOTE TO INSTALLER

When on Balancing Mode, the Selector Switch  

allows you to choose the motor you want to set.
Closed Duotrol Cover 

1. INTER (Exhaust Motor) 

2. CONT (Both Motors) 

3. OFF (Supply Motor)

Step 1

  Press the (+) and (–) buttons on the Duotrol™ simultaneously 

until you see the yellow light. Once the indicator light turns 

yellow and the unit goes to high speed you are in balancing mode. 

When in balancing mode the selector switch on the Duotrol™ 

becomes the motor selector switch: 

INTER = Exhaust Airflow Motor 

CONT = Both Motors 

OFF = Supply Airflow Motor  

Step 2

  To adjust the 

(fresh air)

, select the «OFF» position on the 

Duotrol™. To adjust the airflow rates, press the 

(–)

 button to 

decrease or press the 

(+)

 button to increase the airflow rates 

until you reach the calculated fresh airflow requirements. 

Step 3

  To adjust the 

(stale air)

 select the «INTER» position on the 

Duotrol™. To adjust the airflow rates, press the 

(–)

 button to 

decrease or press the 

(+)

 button to increase the airflow rates 

until you reach the calculated stale airflow requirements. 

Step 4

  Once this is completed and you have balanced the airflow rates 

required for your application. Proceed to exit the balancing 

mode you must press 

(+)

 and 

(–)

 buttons on the Duotrol™ 

simultaneously until solid green LED appears then release. The 

indicator light will turn green to indicate normal operation mode. 

Step 5

  Mark down the balanced air flow rates information. Apply the 

label to the ERV access door for future reference (e.g. date, 

balance airflow rate, your name, phone number and business 

address). 

Step 6

  Once the ERV is balanced, switch to «CONT» on the Duotrol™ 

By using

 (+) 

 and

 (–)

 buttons you can set the continuous speed if 

required. 

Note : 

 

When selecting the 

CONT

 mode: The ERV will continuously exhaust 

stale indoor air to the outside and will introduce fresh outdoor 

air continuously on low speed except when there is a request for 

ventilation by one of the remote controllers then the ventilation system 

will exchange at high speed. 

(Recommended for maximum indoor air 

quality.) 

 

When selecting the 

INTER

 mode: The only ERV will only run on high 

speed when there is a request for ventilation. At this time the unit will 

run on high speed until the level of humidity is below the set point. The 

T-3 timer has completed its time period or once the cycles per hour has 

completed its cycle. 

Duotrol

TM

 System

NOTICE: 

To balance the LCH-12E it will require balancing damper in the ductwork since the Duotrol does not offer this balancing feature at the current moment.

Pitot tube

Magnahelic gauge

Pitot tube

Magnahelic gauge

Note: Insert pitot 
tube minimum 18” 
from unit, blower or 
elbows. The same 
applies when using 
air flow stations.

Содержание LCH-12E

Страница 1: ...entek Greentek reserves the rights to modify a product without prior notice whether in price design color or codes in order to offer at all times quality products that are highly competitive Greentek...

Страница 2: ...ection when disconnecting it from the ventilation system Do not use the ventilation system for removal of flammable fumes or near flammable gases Use a dedicated power source Do not obstruct or cover...

Страница 3: ...otrol System 10 9 Modes of Operations 11 10 Controls Connection 12 11 Maintenance 13 12 Wiring Diagram LCH 4E 14 13 Wiring Diagram LCH 7E 15 14 Wiring Diagram LCH 12E 16 15 Limited Warranty 17 Greente...

Страница 4: ...built on site Connecting appliances to the ERV It is not recommended including clothes dryer kitchen exhaust hoods combustion venting central vacuum system These appliances may cause lint dust or grea...

Страница 5: ...ed in a conditioned space where the temperature is maintained above the freezing point A P trap is required in the drain line This will prevent odors from being drawn back up into the unit Drain Fitti...

Страница 6: ...uct from the weather hoods to the ERV must be fully insulated to minimize heat loss or heat gain and to avoid potential condensation Insulated flex duct may be used in moderation if sized and installe...

Страница 7: ...plication Proceed to exit the balancing mode you must press and buttons on the Duotrol simultaneously until solid green LED appears then release The indicator light will turn green to indicate normal...

Страница 8: ...usting of stale air accumulated in the building Supply air supplied to main living areas ERV airflow must be balanced according to the building s airflow requirements Optional External heating or cool...

Страница 9: ...AIR SUPPLY AIR DUCT SIMPLIFIED SYSTEM INSTALLATION Exhausting of stale air accumulated in the building from the return air duct of the air handler Supply air supplied to the return air duct of the air...

Страница 10: ...til the level of humidity is below the set point The T 3 timer has completed its time period or once the cycles per hour has completed its cycle TIP During hot and humid days it is recommended that yo...

Страница 11: ...sh air to dwelling Stale air to outside Fresh air from outside Stale air from dwelling Stale air to outside Stale air from dwelling Normal Evacuation DEFROST CYCLE TYPES Defrost sequence type Evacuati...

Страница 12: ...ERV Controller Low Voltage ERV Controller Low Voltage ERV Controller Low Voltage ERV Controller Terminal Barrier ERV ERV Connection Terminal Barrier ERV ERV Connection Terminal Barrier ERV ERV Connect...

Страница 13: ...After inspection and cleaning make sure the core is replaced right side up 4 Clean the condensate drain and pan Twice a year check the condensate drain and tubing to ensure that they are open and free...

Страница 14: ...14 LOW SPEEDS 90V 75V J4 J5 J6 12 WIRING DIAGRAM LCH 4E...

Страница 15: ...15 LOW SPEEDS 90V 75V J4 J5 J6 13 WIRING DIAGRAM LCH 7E...

Страница 16: ...16 LOW SPEEDS 90V 75V J4 J5 J6 14 WIRING DIAGRAM LCH 12E...

Страница 17: ...f the previous limited warranty to be free from defects in material and workmanship If a defect is found within one year from date of original installation of replacement part whether or not actual us...

Страница 18: ...50 Kanalflakt Way Bouctouche NB E4S 3M5 1 888 724 5211 Fax 1 866 426 7430 www greentek ca Item 444863...

Страница 19: ...L D INSTALLATION Produit de Greentek Greentek se r serve le droit de modifier un produit sans pr avis soit en prix conception couleur ou code pour offrir en tout temps des produits comp titifs de qual...

Страница 20: ...du syst me de ventilation N utilisez pas le syst me de ventilation pour vacuer des vapeurs inflammables et ne l installez pas proximit de sources de gaz inflammables L appareil doit avoir une source...

Страница 21: ...ions 8 9 8 Fonctionnement du syst me Duotrol 10 9 Modes de fonctionnement 11 10 Connexion des commandes 12 11 Entretien 13 12 Sch ma de c blage LCH 4E 14 13 Sch ma de c blage LCH 7E 15 14 Sch ma de c...

Страница 22: ...otamment s cheuse linge hotte de cuisine appareil produisant des gaz de combustion syst me d aspirateur central Le raccordement de ces appareils peut occasionner une accumulation de poussi re ou de gr...

Страница 23: ...n o la temp rature est maintenue au dessus du point de cong lation Le tuyau doit tre muni d un siphon en P pour viter le refoulement d odeurs dans l appareil Raccord du drain Vers le drain ou la pompe...

Страница 24: ...eaux de protection et le VRE doivent tre enti rement isol es pour r duire au minimum les pertes de chaleur et viter la condensation Des conduits isolants flexibles peuvent tre utilis s avec mod ration...

Страница 25: ...devienne vert Le t moin vert indique que l appareil est maintenant en mode de fonctionnement normal tape 5 Notez les valeurs des d bits d air quilibr s sur une tiquette que vous apposerez sur la trap...

Страница 26: ...r frais distribu dans les principales aires d habitation Le d bit du VRE doit tre quilibr en fonction des besoins de circulation d air de l immeuble Facultatif Serpentin de chauffage ou de refroidisse...

Страница 27: ...UR AIR VACU CONDUIT D AIR D ASPIRATION INSTALLATION SIMPLIFI E vacuation de l air vici de l immeuble par la gaine de retour de l appareil de traitement de l air L air d alimentation est inject dans la...

Страница 28: ...aut r gime quand le taux d humidit a atteint le seuil fix quand la minuterie T 3 est arriv e terme ou quand le nombre de cycles par heure a t atteint CONSEIL Il est recommand de mettre le syst me en m...

Страница 29: ...ir vici vers l ext rieur Air frais de l ext rieur Air vici des aires d habitation Air vici vers l ext rieur Air vici des aires d habitation Normal 2a vacuation 2 Type de s quence de d givrage vacuatio...

Страница 30: ...tension VRE Contr leur basse tension VRE Contr leur basse tension VRE Contr leur basse tension VRE Terminal Barrier HRV ERV Connection Terminal Barrier HRV ERV Connection Terminal Barrier HRV ERV Con...

Страница 31: ...e assurez vous de replacer l changeur dans le bon sens 4 Nettoyez la tuyauterie d vacuation et le collecteur de condensat Deux fois par an inspectez la tuyauterie de condensat qui doit tre propre pour...

Страница 32: ...32 12 SCH MA DE C BLAGE LCH 4E LOW SPEEDS 90V 75V J4 J5 J6...

Страница 33: ...33 13 SCH MA DE C BLAGE LCH 7E LOW SPEEDS 90V 75V J4 J5 J6...

Страница 34: ...34 14 SCH MA DE C BLAGE LCH 12E LOW SPEEDS 90V 75V J4 J5 J6...

Страница 35: ...dans l ann e suivant son installation que son usage ait commenc la journ e de l installation ou non Greentek fournira sans frais une pi ce neuve ou r usin e sa discr tion pour remplacer la pi ce d fe...

Страница 36: ...50 Kanalflakt Way Bouctouche NB E4S 3M5 1 888 724 5211 Fax 1 866 426 7430 www greentek ca Item 444863...

Отзывы: