2

Receiving

Upon receiving the product check to make sure all 

items are accounted for by referencing the bill of 

lading to ensure all items were received. Inspect 

each crate for shipping damage before accepting 

delivery. Notify the carrier if any damage is noticed. 

The carrier will make notification on the delivery 

receipt acknowledging any damage to the product. 

All damage should be noted on all the copies of the 

bill of lading which is countersigned by the delivering 

carrier. A Carrier Inspection Report should be filled 

out by the carrier upon arrival and reported to the 

Traffic Department. If damaged upon arrival, file 

a claim with carrier. Any physical damage to the 

unit after acceptance is not the responsibility of 

Greenheck Fan Corporation. 

Unpacking

Verify that all required parts and the correct quantity 

of each item have been received. If any items are 

missing, report shortages to your local representative 

to arrange for obtaining missing parts. Sometimes it 

is not possible that all items for the unit be shipped 

together due to availability of transportation and truck 

space. Confirmation of shipment(s) must be limited to 

only items on the bill of lading. 

Electrical

The motor amperage and voltage ratings must be 

checked for compatibility to supply voltage prior 

to final electrical connection. Wiring must conform 

to local and national codes. Consult local code 

authorities for specific requirements. 

Storage

Product is protected against damage during 

shipment. If the product cannot be installed and 

operated immediately, precautions need to be 

taken to prevent deterioration of the product during 

storage. The user assumes responsibility of the 

product and accessories while in storage. The 

manufacturer will not be responsible for damage 

during storage. These suggestions are provided 

solely as a convenience to the user. 

Indoor Only

Do not store this product outdoors. The ideal 

environment for the storage of this product is 

indoors, above grade, in a low humidity atmosphere 

which is sealed to prevent the entry of blowing 

dust, rain or snow. Temperatures should be evenly 

maintained between 30° to 110°F (-1° to 43°C) (wide 

temperature swings may cause condensation and 

“sweating” of metal parts). All accessories must be 

stored indoors in a clean, dry atmosphere. 
Remove any accumulations of dirt, water, ice, or 

snow and wipe dry before moving to indoor storage. 

Allow cold parts to reach room temperature to avoid 

“sweating” of metal parts. To dry parts and packages, 

use a portable electric heater to get rid of any moisture 

buildup. Leave coverings loose to permit air circulation 

and to allow for periodic inspection. The unit should 

not be stored on the floor. 

Inspection and Maintenance 

During Storage

While in storage, inspect product once per month. 

Keep a record of inspection and maintenance 

performed. If moisture or dirt accumulations are found 

on parts, the source should be located and eliminated. 

Installation and Setup Guide

This guide provides instructions for how to 

install, wire and program the control system for 

use when constant pressure in a duct or room 

system is required. This does not cover ductwork 

recommendations or other considerations. 

Electrical Safety Information 

Follow all local electrical and safety codes, as well 

as the National Electrical Code (NEC) and the 

National Fire Protection Agency (NFPA). Where 

applicable, follow the Canadian Electric Code.
1.  The rotation of the wheel is critical. It must be 

free to rotate without striking or rubbing any 

stationary objects.

2.  Motor must be securely and adequately 

grounded.

3.  Do not spin fan wheel faster than maximum 

cataloged fan RPM. Adjustment to fan speed 

significantly affects motor load. If fan RPM is 

changed, motor current should be checked 

to make sure it is not exceeding the motor 

nameplate amps.

4.  Do not allow the power cable to kink or come 

in contact with oil, grease, hot surfaces, 

or chemicals. Replace cord immediately if 

damaged.

5.  Verify that the power source is compatible with  

the equipment.

6.  Never open access doors to a duct while the  fan 

is running.

Содержание Vari-Green Air Quality VOC

Страница 1: ...he Vari Green motor technology to operate quietly and efficiently The VOC controller has adjustments for air quality setpoint and minimum and maximum fan speed The fan speed and VOC level are availabl...

Страница 2: ...age of this product is indoors above grade in a low humidity atmosphere which is sealed to prevent the entry of blowing dust rain or snow Temperatures should be evenly maintained between 30 to 110 F 1...

Страница 3: ...wo 3 16 inch holes in the center of each marked mounting hole DO NOT punch the holes or the drywall anchors will not hold Insert a drywall anchor into each hole 5 Drill one 1 2 inch hole in the middle...

Страница 4: ...e scroll button switches the display to the Fan Speed in percent SPD and a third push returns the display to the VOC Level VOC Minor Display 0 34 inch 3 digit Alpha Numeric Main Display 0 76 inch 4 di...

Страница 5: ...19 jumper on a single pin Parameter Display Description Default Setting Air Quality Setpoint 40 Factory Defaults 0 See Below Display Units 2 Air Quality in VOCs Fan Cutout Enable 0 Fan Cutout Disabled...

Страница 6: ...Fan Icon on the display will turn on and the minor display will show OVR and the main display will show the Fan Speed Output percent value Output State Parameter P6 Factory Default 1 0 Manual Control...

Страница 7: ...point may be too low for persistent background VOCs Check the space for a spill Setpoint may be too low for persistent background VOCs If the controller will not turn the fan off verify that the measu...

Страница 8: ...rial and workmanship for a period of one year from the shipment date Any units or parts which prove defective during the warranty period will be replaced at our option when returned to our factory tra...