background image

3

Mounting

Mount the controller in the space to be controlled. 

Keep wire lengths between the controller and the fan 

to 200 feet or less.

1.  Separate the unit from the back plate by driving 

in the Allen screw until the two pieces come free. 

2.  Pull the wire through the wall and out of the 

junction box, leaving about six inches free.

3.  Pull the wire through the hole in the base plate.
4.  Secure the plate to the box using the #6-32 x 5/8 

inch mounting screws provided.

5.  Terminate the unit wiring.
6.  Mold the foam on the unit’s base to the wire 

bundle to prevent drafts. (see note below)

7.  Attach Cover by latching it to the top of the base, 

rotating the cover down and snapping it into place.

8.  Secure the cover by backing out the lock-down 

screw using a 1/16 inch Allen wrench until it is 

flush with the bottom of the cover.

1.  Separate the unit from the back plate by driving 

in the Allen screw until the two pieces come free. 

2.  Place the base plate against the wall where you 

want to mount the sensor.

3.  Using a pencil mark out the two mounting holes 

and the area where the wires will come through 

the wall.

4.  Drill two 3/16 inch holes in the center of each 

marked mounting hole, DO NOT punch the 

holes or the drywall anchors will not hold. Insert 

a drywall anchor into each hole.

5.  Drill one 1/2 inch hole in the middle of the 

marked wiring area.

6.  Pull the wire through the wall and out of the 1/2 

Inch hole, leaving about six inches free.

7.  Pull the wire through the hole in the base plate.
8.  Secure the base to the drywall anchors using the 

#6 x 1 inch mounting screws provided.

9.  Terminate the unit wiring.
10. Mold the foam on the unit’s base to the wire 

bundle to prevent drafts. (see note below)

11.  Attach cover by latching it to the top of the base, 

rotating the cover down and snapping it into place.

12. Secure the cover by backing out the lock-down 

screw using a 1/16 inch Allen wrench until it is 

flush with the bottom of the cover.
NOTE:  In any wall-mount application, the air 

within the wall cavity can cause erroneous 

readings. The mixing of room air and air from 

within the wall cavity can lead to condensation, 

erroneous readings and sensor failure. 

To prevent these conditions, Greenheck 

recommends sealing the conduit leading to 

the junction box, filling the junction box with 

fiberglass insulation or sealing the wall cavity.

Electrical Box

Mounting Plate

Cover

Junction Box Mounting

Mounting Plate

Cover

Drywall Mounting

Содержание Vari-Green Air Quality VOC

Страница 1: ...he Vari Green motor technology to operate quietly and efficiently The VOC controller has adjustments for air quality setpoint and minimum and maximum fan speed The fan speed and VOC level are availabl...

Страница 2: ...age of this product is indoors above grade in a low humidity atmosphere which is sealed to prevent the entry of blowing dust rain or snow Temperatures should be evenly maintained between 30 to 110 F 1...

Страница 3: ...wo 3 16 inch holes in the center of each marked mounting hole DO NOT punch the holes or the drywall anchors will not hold Insert a drywall anchor into each hole 5 Drill one 1 2 inch hole in the middle...

Страница 4: ...e scroll button switches the display to the Fan Speed in percent SPD and a third push returns the display to the VOC Level VOC Minor Display 0 34 inch 3 digit Alpha Numeric Main Display 0 76 inch 4 di...

Страница 5: ...19 jumper on a single pin Parameter Display Description Default Setting Air Quality Setpoint 40 Factory Defaults 0 See Below Display Units 2 Air Quality in VOCs Fan Cutout Enable 0 Fan Cutout Disabled...

Страница 6: ...Fan Icon on the display will turn on and the minor display will show OVR and the main display will show the Fan Speed Output percent value Output State Parameter P6 Factory Default 1 0 Manual Control...

Страница 7: ...point may be too low for persistent background VOCs Check the space for a spill Setpoint may be too low for persistent background VOCs If the controller will not turn the fan off verify that the measu...

Страница 8: ...rial and workmanship for a period of one year from the shipment date Any units or parts which prove defective during the warranty period will be replaced at our option when returned to our factory tra...

Отзывы: