Ceiling Exhaust Fan Support

The following two mounting methods may be used.
1.  Suspend fan/damper assembly using #10-32 

threaded steel rod as shown in 

Figure 4

. Suspend 

from joists or cold rolled channels (do not suspend 
from beams). If vibration isolators are used, fender 
washers must have a larger outside diameter than 
the holes in the fan mounting angle.

2.  Support fan/damper assembly using (2) minimum 

16 ga. x 1

1

2

 in. steel channels with 

9

16

 in. flanges. 

Suspend from joists or cold rolled channels (do not 
suspend from beams). Alternatively, bolt channels 
ends directly to joists or other cold rolled channels 
using minimum #10 bolts. See 

Figure 5

.

Do NOT support fan/damper assembly by ceiling 
tile or ceiling grid (Tee) members when using with a 
suspended ceiling!

UL/cUL Installation - 3 Hour Non Combustible Floor/Ceiling Assemblies

SP Fan

#10-32 Threaded

Steel Rod

Hanging Vibration 

Isolation
Ceiling Radiation

Damper

Fire Rated Ceiling

3 in .

Grille

Hole Opening Is

“A” x “B”

#10 x ¾ in. SMS 

6 in. Max. Centers,

2 Min./Side

Beam

Steel

Joists

Steel Hanger Wires

(12 SWG minimum)

Concrete Floor

Figure 3

“D”

“E”

Figure 4

Figure 5

#10 Bolt or #10-32 

Threaded Steel Rod

Supports To Joists Or

Other Cold Formed

Channels (By Others)

1 1/2 in. x 9/16 in. x 16 Gauge 

(Minimum) Cold Formed Steel

#10 x 3/8 in. SMS, 

(Minimum) 4 Per Side

CRD-XXX

Series Damper

#10 Bolt or Sheet Metal Screw
(Minimum) Attached Through
Prepunched Holes In Mounting 
Angles Into Channel Brace 
Supports, 2 Per Side (By Others)

Grille Installation

Mount grille to underside of ceiling radiation damper 
using 2 - #10 x 

1

2

 in. Phillips head stainless steel sheet 

metal screws provided with SP fan.

CRD Series for SP Fans

7

®

Содержание CRD-3 Series

Страница 1: ...D 700 Series for SP Fans Installation Operation and Maintenance Manual Please read and save these instructions for future reference Read carefully before attempting to assemble install operate or main...

Страница 2: ...Motors for fan models used in conjunction with CRD shall be equipped with thermal cut off fuse control Receiving and Handling Upon receiving dampers check for both obvious and hidden damage If damage...

Страница 3: ...he assembly around the damper in the orientation shown in Figure 1 Connect the open ends of the flange together 2 Align the edge of the plaster flange with the edge of the damper frame Clamp the flang...

Страница 4: ...B200 CRD 320 CRD 320L CRD 320 41 2 155 8 141 2 123 8 SP A50 SP A70 SP A90 SP A110 SP A125 SP A190 CRD 310WT CRD 310 CRD 310L CRD 310 WT CRD 310 51 2 145 8 135 8 111 8 SP A250 SP A290 SP A390 SP A200...

Страница 5: ...with the unit 2 The fan damper assembly is to be attached to the trusses using 2 1 in x 1 in x 16 ga 25mm x 25mm x 1 5mm or 2 11 4 in x 1 in x 20 ga 32mm x 25mm x 1mm mounting angles Attach mounting...

Страница 6: ...minimum of 2 8 screws or 5 32 in 4mm diameter steel rivets Note Make sure the fasteners do not interfere with the damper operation 3 Install the fan damper assembly with attached mounting angles betwe...

Страница 7: ...when using with a suspended ceiling UL cUL Installation 3 Hour Non Combustible Floor Ceiling Assemblies SP Fan 10 32 Threaded Steel Rod Hanging Vibration Isolation Ceiling Radiation Damper Fire Rated...

Страница 8: ...eals Adjust frame such that it is square and plumb Screws in damper linkage Damper installed too far into wall Move out to line as designated on damper label Contaminants on damper Clean with a non oi...

Отзывы: