Plaster Flange Application

Note: The plaster flange is required when the 
damper is installed in a combustible floor/ceiling 
assembly.

When the damper is installed in a non-combustible 
ceiling/floor assembly, the plaster flange is not required 
and can be discarded. When unpacking the flange 
kit from the damper, remove all tape residue from the 
damper and plaster flange.
When the plaster flange is required, the flange assembly 
must be attached to the damper as follows.
1.  Unfold the plaster flange assembly that is supplied. 

Wrap the assembly around the damper in the 
orientation shown in 

Figure 1

. Connect the open 

ends of the flange together.

2.  Align the edge of the plaster flange with the edge of 

the damper frame. Clamp the flange to the damper 
frame.

3.  Using the flange holes as a guide, secure the flange 

to the damper frame using the supplied fasteners. 
Install fasteners within 1

1

2

 inches (38mm) from each 

corner first, then at or near the center of each damper 
side. Install a fastener on both sides of the grille 
mounting tabs. Be careful to not strip out the damper 
frame material while installing the fasteners. 

Width

Height

CRD Damper

Grill Mounting Tab

Plaster Flange

TEK Screws
14 PLCS

Figure 1: CRD damper with plaster flange

CRD Series for SP Fans

3

®

Содержание CRD-3 Series

Страница 1: ...D 700 Series for SP Fans Installation Operation and Maintenance Manual Please read and save these instructions for future reference Read carefully before attempting to assemble install operate or main...

Страница 2: ...Motors for fan models used in conjunction with CRD shall be equipped with thermal cut off fuse control Receiving and Handling Upon receiving dampers check for both obvious and hidden damage If damage...

Страница 3: ...he assembly around the damper in the orientation shown in Figure 1 Connect the open ends of the flange together 2 Align the edge of the plaster flange with the edge of the damper frame Clamp the flang...

Страница 4: ...B200 CRD 320 CRD 320L CRD 320 41 2 155 8 141 2 123 8 SP A50 SP A70 SP A90 SP A110 SP A125 SP A190 CRD 310WT CRD 310 CRD 310L CRD 310 WT CRD 310 51 2 145 8 135 8 111 8 SP A250 SP A290 SP A390 SP A200...

Страница 5: ...with the unit 2 The fan damper assembly is to be attached to the trusses using 2 1 in x 1 in x 16 ga 25mm x 25mm x 1 5mm or 2 11 4 in x 1 in x 20 ga 32mm x 25mm x 1mm mounting angles Attach mounting...

Страница 6: ...minimum of 2 8 screws or 5 32 in 4mm diameter steel rivets Note Make sure the fasteners do not interfere with the damper operation 3 Install the fan damper assembly with attached mounting angles betwe...

Страница 7: ...when using with a suspended ceiling UL cUL Installation 3 Hour Non Combustible Floor Ceiling Assemblies SP Fan 10 32 Threaded Steel Rod Hanging Vibration Isolation Ceiling Radiation Damper Fire Rated...

Страница 8: ...eals Adjust frame such that it is square and plumb Screws in damper linkage Damper installed too far into wall Move out to line as designated on damper label Contaminants on damper Clean with a non oi...

Отзывы: