5

Ducted Outlet Installations

Discharge Duct Turns

 - Duct turns located near the 

fan discharge should always be in the direction of the 
fan rotation.

Fan performance is reduced when duct 
turns are made immediately off the 
fan discharge. To achieve cataloged 
fan performance there 
should be at least 
three equivalent 
duct diameters of 
straight ductwork 
between the fan 
discharge and 
any duct turns.

Inlet Spin 

- Inlet spin is a frequent cause of reduced 

fan performance. The change in fan performance is a 
function of the intensity of spin and not easily defined. 
The best solution is proper duct design and airflow 
patterns. Turning vanes reduce the effects of inlet spin.

3/4 to 

one fan

wheel

diameter

One fan

diameter

3/4 to 

one fan

wheel

diameter

Parallel Fan Installation

Non-Ducted Installations

Inlet Clearance

 - Installation of a fan with an open 

inlet too close to a wall or bulkhead will cause reduced 
fan performance. It is desirable to have one fan wheel 
diameter between parallel fan units and a minimum of 
three-fourths of a wheel diameter between the fan inlet 
and the wall.

Free Discharge

 - Free or abrupt discharge into a 

plenum results in a reduction in fan performance. The 
effect of discharge static regain is not realized.

Rota

tio

n

Rota

tio

n

Turning

Vanes

POOR

GOOD

Ducted Inlet Installations 

Inlet Duct Turns

 - Installation of a duct turn or elbow 

too close to the fan inlet reduces fan performance 
because air is loaded 
unevenly into the fan 
wheel. To achieve full fan 
performance, there should 
be at least three fan wheel 
diameters between the turn 
or elbow and the fan inlet.

POOR

Turning

Vanes

GOOD

Three fan wheel diameters

Move the fan to the desired location. Check and tighten 
fasteners throughout the unit and then fasten securely 
through mounting holes provided in the base angles. 
The unit must be set level (shimming may be necessary). 
Flexible duct connections and vibration isolators should 
be used where noise is a factor.

The motor voltage and ampere rating must be checked 
for compatibility with the electrical supply prior to final 
electrical connection. Supply wiring to the fan must 
be properly fused, and conform to local and national 
electrical codes.

Installations with inlet or discharge configurations that 
deviate from this standard may result in reduced fan 
performance. Restricted or unstable flow at the fan 
inlet can cause pre-rotation of incoming air or uneven 
loading of the fan wheel yielding large system losses 
and increased sound levels. Free discharge or turbulent 
flow in the discharge ductwork will also result in system 
effect losses. Refer to the following diagrams for the 
most efficient installation conditions.

R

o

ta

tion

R

o

ta

tion

POOR

Length of Straight Duct

GOOD

3/4 to one

 fan

wheel

diameter

3/4 to one

fan

wheel

diameter

Single Fan Installation

Installation

Содержание AFDW

Страница 1: ...ore moving forward 1 Follow all local electrical and safety codes as well as the National Electrical Code NEC the National Fire Protection Agency NFPA where applicable Follow the Canadian Electric Cod...

Страница 2: ...he surfaces Wipe clean thoroughly with Tectyl 506 Ashland Inc or the equivalent For hard to reach internal surfaces or for occasional use consider using Tectyl 511M Rust Preventive or WD 40 or the equ...

Страница 3: ...alled and secure Do not spin fan wheel faster than the maximum cataloged fan RPM Adjustments to fan speed signi cantly affects motor load If the fan RPM is changed the motor current should be checked...

Страница 4: ...rs are recommended to prevent damage to the unit Failure to use spreader bars may result in damage which becomes the installer s responsibility Guards Motor Cover Weatherhood Shaft Belt Inlet or Outle...

Страница 5: ...cted Inlet Installations Inlet Duct Turns Installation of a duct turn or elbow too close to the fan inlet reduces fan performance because air is loaded unevenly into the fan wheel To achieve full fan...

Страница 6: ...ding vibration isolators should be used The fan is mounted directly on the isolation base and must be supported for the entire length of the fan base angle Refer to the Centrifugal Fan Isolation Base...

Страница 7: ...ment points for belt guard mounting bracket locations These locations vary with motor mounting position arrangement and fan type The bearing supports and fan structure are used in most instances and w...

Страница 8: ...bolts and centering the wheel is acceptable as a secondary option Overlap or offset is adjusted by loosening the wheel hub from the shaft and moving the wheel to the desired position along the shaft...

Страница 9: ...tructural and or component failure Many of these conditions can be discovered by careful observation Refer to the troubleshooting section of this manual for corrective actions If observation cannot lo...

Страница 10: ...s Bearings are the most critical moving part of the fan therefore special care is required when mounting them on the unit and maintaining them Refer to the following chart and the manufacturers instru...

Страница 11: ...Application Guide FA 127 11 Measuring Belt Tension found online at greenheck com in the Resources section Check belt tension before start up and after the rst 24 hours of operation The belt tension sh...

Страница 12: ...data sheet Four disposable foam brushes One sheet sandpaper Repair procedure details NOTE While the manufacturer provides heavy duty quality products for marine environments routine paint touch ups ma...

Страница 13: ...CAUTION A fan manufactured with an explosion resistant motor does not certify the entire unit to be explosion proof Refer to UL Listing Mark for the fans approved usage Each fan bears a manufacturer...

Страница 14: ...nd Filtered Supply 14 Industrial Process Heat Slinger Weatherhood Arrangement 10 only Volume Control Damper Outlet Companion Flange Outlet Flange Inlet Flange Inlet Companion Flange Shaft Bearings Bel...

Страница 15: ...d or new lters are ready to be installed place the lters back into the racks in the reverse order of which they were removed When all lters are in place close and secure the top roof panels High Horse...

Страница 16: ..._____Time _____________ AM PM Notes ___________________________________________ _________________________________________________ _________________________________________________ ____________________...

Отзывы: