Wired Controller XE70-33/H
46
“ ” button to adjust the air level 1~10, and then press “ ” button to save the setting
and return to the previous page.
NOTES:
①
Air function is applicable only to units with air function and installed with
fresh air electric valve (fresh air valve in short).
②
Air level is related to the opening time of fresh air valve in a certain time (60
minutes). Please see the table below. Opening time of fresh air valve
indicates the first N minutes within a certain time. For example: if air degree
is set to 1, unit starts to count the time and fresh air valve is open. 6 minutes
later, fresh air valve is closed while unit continues operating. When the unit
counts to 60 minutes, it will restart counting and fresh air valve is open. 6
minutes later, fresh air valve is closed. Unit operates circularly like this.
Air
Level
1
2
3
4
5
6
7
8
9
10
Time for
opening
of fresh
air valve
60/6 60/12 60/18 60/24 60/30 60/36 60/42 60/48 60/54
Constantly
open
NOTE:
the time in the table means: operating time of unit (minute)/opening time of fresh air valve
during the operating period of unit (minute)
7.6.3 Setting of Save Function
Save: through setting the lower limit value of set temperature for Cool, Dry,
modes and upper limit of set temperature for Heat, 3D Heat, Space modes, to make
the air conditioner operate in a smaller temperature range, so as to achieve energy