38
Air to Water Heat Pump
Service Manual- Versati II Series
INSTALLATION
Step3: Attaching indoor unit to the wall make use of accessory expansion bolt.
Expansion bolt
Install wall
!
CAUTION!
While lifting the indoor unit, at least two persons should be joined. Weight of the indoor unit is almost 52kg.
Precautions on Installation of Indoor Unit
1
Indoor unit shall be vertically mounted on the wall of the room with expansion bolt.
2
Keep the Indoor unit away from heat sources such as heat sink and so on in the room as much as
possible.
3
Keep the indoor unit as close as possible to outdoor unit. Level distance between connection pipes can
not exceed 30m and vertical distance can not exceed 15m.
1.3.3 Installation of Insulated Water Tank
1�3�3�1 Installation Measure
The insulated water tank should be installed and keep levelly within 5m and vertically within 3m from the
Indoor unit. It can be installed in the room.
Standing water tank must be installed vertically with the bottom on the ground, never suspended.
Installation place must be firm enough and the water tank should be fixed on the wall with bolts to avoid
vibration, as shown in the following figure. Weight capacity of water tank during installation should also be
considered.
Fix
with
bolts
Water tank
Installed on the ground and never suspended
Содержание Versati II
Страница 1: ...AIR TO WATER HEAT PUMP SERVICE MANUAL Versati T1 R410A 50Hz GC201308 II ...
Страница 4: ...1 Air to Water Heat Pump Service Manual Versati II Series PRODUCT PRODUCT ...
Страница 13: ...10 Air to Water Heat Pump Service Manual Versati II Series CONTROL CONTROL ...
Страница 37: ...34 Air to Water Heat Pump Service Manual Versati II Series INSTALLATION INSTALLATION ...
Страница 62: ...59 Air to Water Heat Pump Service Manual Versati II Series MAINTENANCE MAINTENANCE ...
Страница 81: ...78 Air to Water Heat Pump Service Manual Versati II Series MAINTENANCE Fig 14 ...
Страница 97: ...JF00301971 ...