25
Air to Water Heat Pump
Service Manual- Versati II Series
CONTROL
[Notes]
①
When “
Floor debug
” or “
Emergen� Mode
” is activated, then the control will not receive signals from the
thermostat.
②
If “Thermostat” is set to “
On
”, the control will automatically disable some functions concerning timer, and
run in accordance with the mode set by the thermostat. In this case, the running mode is unchangeable and the
ON/OFF key operation of the control is ineffective.
③
When this setting is saved successfully, it will be memorized upon power failure.
④
The state of the Thermostat can be changed when the unit is turned off.
3�3�2�19 IDU Heater
Go to the
FUNCTION
page and locate “
IDU Heater
”, then, configure it through the Up/Down key, “
With
” or
“
Without
”.
[Notes]
it will be memorized upon power failure.
3�3�2�20 Other Heater
Go to the
FUNCTION
page and locate
Other heater
, then, configure it through the Up/Down key, “
With
” or
“
Without
”.
[Notes]
it will be memorized upon power failure.
3�3�2�21 Underpan Heater
Go to the
FUNCTION
page and locate “
Underpan Heater
” then, configure it through the Up/Down key, “
With
”
or “
Without
”.
[Notes]
it will be memorized upon power failure.
3�3�2�22 Water Tank
Go to the
FUNCTION
page and locate “
Water tank
” then, configure it through the Up/Down key, “
With
” or
“
Without
”.
[Notes]
①
It will be memorized upon power failure.
②
This setting is allowed only when the unit is turned off.
3�3�2�23 Tank Sensor
Go to the
FUNCTION
page and locate “
Water tank
”, then, configure it through the Up/Down key, “
1
” or “
2
”.
When the water tank is unavailable, this option will be reserved.
[Notes]
it will be memorized upon power failure.
3�3�2�24 Solar Heater
Go to the
FUNCTION
page and locate “
Solar heater
”, then, configure it through the Up/Down key, “
With
” or
“
Without
”.
[Notes]
it will be memorized upon power failure.
3�3�2�25 FCU
Go to the
FUNCTION
page and locate “
FCU
”, then, configure it through the Up/Down key, “
With
” or
“
Without
”.
[Notes]
It will be memorized upon power failure.
3�3�2�26 Remote Sensor
Go to the
FUNCTION
page and locate “
Remote sensor
”, then, configure it through the Up/Down key, “
With
”
or “
Without
”.
[Notes]
It will be memorized upon power failure.
“
T-room ctrl
” can be selected only when the Remote Sensor is set to “
With
”.
3�3�2�27 Air removal
Go to the
FUNCTION
page and locate “
Air removal
”, then, configure it through the Up/Down key, “
On
” or
“
Off
”.
[Notes]
①
It will not be memorized upon power failure.
②
It can be set only when the unit is turned off.
Содержание Versati II
Страница 1: ...AIR TO WATER HEAT PUMP SERVICE MANUAL Versati T1 R410A 50Hz GC201308 II ...
Страница 4: ...1 Air to Water Heat Pump Service Manual Versati II Series PRODUCT PRODUCT ...
Страница 13: ...10 Air to Water Heat Pump Service Manual Versati II Series CONTROL CONTROL ...
Страница 37: ...34 Air to Water Heat Pump Service Manual Versati II Series INSTALLATION INSTALLATION ...
Страница 62: ...59 Air to Water Heat Pump Service Manual Versati II Series MAINTENANCE MAINTENANCE ...
Страница 81: ...78 Air to Water Heat Pump Service Manual Versati II Series MAINTENANCE Fig 14 ...
Страница 97: ...JF00301971 ...