27
Air to Water Heat Pump
Service Manual- Versati II Series
CONTROL
No� Full Name
Displayed
Name
Range(
℃
)
Range
(
℉
)
Default
1
Water out temperature
for cooling
WOT-Cool
7~25
℃
[With FCU]
18~25
℃
[Without FCU]
45~77
℉
[With FCU]
64~77
℉
[Without FCU]
7
℃
/45
℉
[With FCU]
18
℃
/64
℉
[Without FCU]
2
Water out temperature
for heating
WOT-Heat
25~55
℃
[High temp.]
25~45
℃
[Low temp.]
77~131
℉
[High temp.]
77~113
℉
[Low temp.]
45
℃
/113
℉
[High temp.]
35
℃
/95
℉
[Low temp.]
3
Room temperature for
cooling
RT-Cool
18~30
℃
64~86
℉
20
℃
/68
℉
4
Room temperature for
heating
RT-Heat
18~30
℃
64~86
℉
26
℃
/79
℉
5
Tank temperature
T-water tank
40~80
℃
104~176
℉
50
℃
/122
℉
6
Eheater-on ambient
temperature
T-Eheater
-20~18
℃
-4~64
℉
0
℃
/32
℉
7
Extra-heater-on
ambient temperature
T-Extraheater
-20~18
℃
-4~64
℉
0
℃
/32
℉
8
Max heat pump
waterout temperature
(no eheater)
T-HP Max
40~50
℃
104~122
℉
50
℃
/122
℉
9
Lower limit ambient
temperature at the auto
mode for heating
Lower AT-Heat
-20~5
℃
-4~41
℉
-15
℃
/5
℉
10
Upper limit temperature
at the auto mode for
heating
Upper AT-Heat
10~20
℃
50~68
℉
15
℃
/59
℉
11
Upper limit room
temperature at the auto
mode for heating
Upper RT-Heat
22~30
℃
72~86
℉
24
℃
/75
℉
12
Lower limit room
temperature at the auto
mode for heating
Lower RT-Heat
18~21
℃
64~70
℉
20
℃
/68
℉
13
Upper limit water-out
temperature at the auto
mode for heating
Upper WT-Heat
46~55
℃
[High temp.]
30~35
℃
[Low temp.]
115~131
℉
[High temp.]
86~95
℉
[Low temp.]
48
℃
/118
℉
[High temp.]
35
℃
/95
℉
[Low temp.]
14
Lower limit water-out
temperature at the auto
mode for heating
Lower WT-Heat
36~45
℃
[High temp.]
25~29
℃
[Low temp.]
97~113
℉
[High temp.]
77~84
℉
[Low temp.]
40
℃
/104
℉
[High temp.]
29
℃
/84
℉
[Low temp.]
15
Lower limit ambient
temperature at the auto
mode for cooling
Lower AT-Cool
10~25
℃
50~77
℉
25
℃
/77
℉
16
Upper limit temperature
at the auto mode for
cooling
Upper AT-Cool
26~48
℃
79~118
℉
40
℃
/104
℉
17
Upper limit room
temperature at the auto
mode for cooling
Upper RT-Cool
24~30
℃
75~86
℉
27
℃
/81
℉
18
Lower limit room
temperature at the auto
mode for cooling
Lower RT-Cool
18~23
℃
64~73
℉
22
℃
/72
℉
19
Upper limit water-out
temperature at the auto
mode for cooling
Upper WT-Cool
15~25
℃
[With FCU]
22~25
℃
[Without FCU]
59~77
℉
[With FCU]
72~77
℉
[Without FCU]
15
℃
/59
℉
[With FCU]
23
℃
/73
℉
[Without FCU]
20
Lower limit water-out
temperature at the auto
mode for cooling
Lower WT-Cool
7~14
℃
[With FCU]
18~21
℃
[Without FCU]
45~57
℉
[With FCU]
64~70
℉
[Without FCU]
7
℃
/45
℉
[With FCU]
18
℃
/64
℉
[Without FCU]
21
Temperature deviation
for cooling
△
T-Cool
2~10
℃
36~50
℉
5
℃
/41
℉
22
Temperature deviation
for heatling
△
T-Heat
2~10
℃
36~50
℉
10
℃
/50
℉
23
Temperature deviation
for heating water
△
T-hot water
2~8
℃
36~46
℉
5
℃
/41
℉
Содержание Versati II
Страница 1: ...AIR TO WATER HEAT PUMP SERVICE MANUAL Versati T1 R410A 50Hz GC201308 II ...
Страница 4: ...1 Air to Water Heat Pump Service Manual Versati II Series PRODUCT PRODUCT ...
Страница 13: ...10 Air to Water Heat Pump Service Manual Versati II Series CONTROL CONTROL ...
Страница 37: ...34 Air to Water Heat Pump Service Manual Versati II Series INSTALLATION INSTALLATION ...
Страница 62: ...59 Air to Water Heat Pump Service Manual Versati II Series MAINTENANCE MAINTENANCE ...
Страница 81: ...78 Air to Water Heat Pump Service Manual Versati II Series MAINTENANCE Fig 14 ...
Страница 97: ...JF00301971 ...