16
Technical Information
Service Manual
①
Operation condition and process for fan mode
In fan mode, the IDU fan motor operates at set speed, while the compressor and the ODU fan motor stop. 4-way valve is de-energized
(4-way valve is not available for cooling only unit). Temperature setting range is 16~30
℃
.
②
Display: Operation icon, set temperature.
③
Protection function
In fan mode, there are overcurrent protection and blocked protection of IDU fan motor. Please refer to corresponding protection function
under cooling mode for details.
(5) Heating mode(no heating mode is not available for cooling only unit)
①
Operation conditioner and process for heating mode
◆
When Tamb-Tcompensation≤Tpreset-1
℃
, unit will operate in heating mode. 4-way valve will be energized while compressor and
outdoor fan starts operation at the same time. Indoor fan will start some time later so that air condition won’t blow out cold air.
◆
When Tamb-Tcompensation≥1
℃
, compressor and outdoor fan will stop operation while 4-way valve is still power on. Indoor
fan will continue operation for a while at set fan speed to blow out the residual heat so that temperature within the air conditioner won’t
be too high.
◆
When Tpreset-1
℃<
Tamb-Tcompensation
<
1
℃
, system will maintain its previous working status.
In heating mode, 4-way valve is energized. Temperature setting range is 16~30
℃
.
②
Display: Operation icon, heating icon, set temperature.
③
Defrosting condition and process
For ensusing heating effect, air conditioner will defrost automatically according to defrosting status on outdoor unit. During defrosting,
heating icon will be on and off.
④
Protection function
◆
Overheating prevention protection
During operation, when controller detects that Ttube≥55
℃
,the ODU fan motor stops operation; When Ttube is resumed normally, the
ODU fan motor resumes operation.
◆
Noise silencing protection
When turning off the unit or during mode switchover, the 4-way valve is closed. In order to decrease noise, the 4-way valve will delay
2mins to be closed.
◆
Overcurrent protection ( this protection function is not available for those models whose cooling capacity ≤12000Btu/h)
During operation process, if controller detected that system current exceeds the limit value for 3s consecutively(overcurrent), the
system stops operation. About 3mins later, if overcurrent is released, the system will resume original operation. If overcurrent protection
occurs for 6 times consecutively, and resume operation time won’t exceed 6min every time, overcurrent protection information will be
displayed. After turning off the unit, display won’t be displayed.
If turn on the unit again, the system will be restated up again. Overcurrent protection information will be eliminated.
Please refer to maintenance part for display information and disposal method for details.
◆
Locked protection to IDU fan motor
During operation of IDU fan motor, if controller detected that the rotation speed of IDU fan motor less than 300/min or stop rotation, the
motor operates abnormally. In order to prevent damage to motor, controller will protect automatically, the system stops operation and
blocked information of IDU fan motor will be displayed. After turning off the unit, display won’t be displayed.
If turn on the unit again, the system will be restated up again. Blocked information of IDU fan motor will be eliminated. (For some mod
-
els, they can only be restated up after re-energized)
Please refer to maintenance part for display information and disposal method for details.
3. Other Control Function Introduction
(1)Timer function
T
preset
+4
T
preset
+2
Stop heating
Original operating status
Start heating
valve
Outdoor unit
Intdoor unit
Compressor
min.
min.
min.
T
amb
.
.
n
i
m
.
n
i
m
Set fan speed
Set fan speed
Reversing