6TQWDNGUJQQVKPI
Energize and
switch on
IPM protection
occurs after the
machine has run for
a period of time?
Use AC voltmeter
to measure the
voltage between
terminal L and N
on the wiring
board XT)
If the voltage
between terminal L
and N on wiring
board XT is within
210VAC~250VAC?
Check the supply
voltage and
restore it to
210VAC~250VAC
Voltage between
the two ends of
electrolytic
capacitor (test3) is
higher than 250V
Restart the
unit. Before
protection occurs,
use DC voltmeter to
measure the voltage
between the two
ends of electrolytic
capacitor on control
panel AP1 (test3)
If the unit can
work
normally?
Please confirm:
1. If the indoor and
outdoor heat
exchangers are
dirty? If they are
obstructed by other
objects which affect
the heat exchange
of indoor and
outdoor unit.
2. If the indoor and
outdoor fans are
working normally?
3. If the environment
temperature is too
high, resulting in
that the system
pressure is too high
and exceeds the
permissible range?
4. If the charge
volume of
refrigerant is too
much, resulting in
that the system
pressure is too
high?
5. Other conditions
resulting in that the
system pressure
becomes too high.
The connection
of capacitor C2
is loose.
Stop the unit and disconnect
the power supply.Then
check the connection of
capacitor C2 according
to Electrical Wiring Diagram.
Reconnect the
capacitor C2 according
to Electrical Wiring
Diagram. Then,
Restart the
unit.
Remove the wires
on the two ends of
capacitor C2. Then,
use capacitance
meter to measure
the capacitor C2.
Verify as per the
Parameters Sheet.
Stop the unit and
disconnect the power
supply. Wait 20 minutes,
or use DC voltmeter to
measure the voltage
between the two ends of
capacitor C2, until the
voltage is lower than 20V
If capacitor
C2 is failed?
Replace the capacitor
C2. Then, energize
and start the unit.
Replace the
control panel AP1
Take corrective actions
according to Technical
Service Manual, and
then energize and start
the unit.
If there is any
abnormality
described above?
Refer to the
Electrical Wiring
Diagram and check
if the connection
between AP1 and
COMP is loose and if
the connection order
is correct.
Replace the
control panel AP1
If the connection
between AP1 and
COMP is unsecure
or the connection
order is wrong?
Connect the control panel
AP1 and compressor
COMP correctly according
to the Electrical Wiring
Diagram. Then, energize
and start
the unit.
Use ohmmeter to
measure the resistance
between the three
terminals on compressor
COMP, and compare the
measurements with the
compressor resistance on
Service Manual.
If the
resistance is
normal?
Use ohmmeter to
measure the resistance
between the two
terminals of compressor
COMP and copper tube.
Replace the
compressor
COMP
Resistance higher
than 500MΩ?
Replace the
control panel
AP1
END
Y
N
Y
N
Y
N
Y
If the unit can
work
normally?
Y
If the unit can
work
normally?
Y
N
N
Y
N
If the unit can
work
normally?
Y
Y
N
N
If the unit can
work
normally?
Y
Y
N
Y
N
N
Y
Содержание GWH18RC-K3DNA1A
Страница 15: ... QPUVTWEVKQP 8KGYU RQVWUXFWLRQ 9LHZV QGRRU 8QLW ĭ ĭ 0RGHO 8QLW PP ĭ ĭ ...
Страница 16: ... QPUVTWEVKQP 8KGYU 2XWGRRU 8QLW 8QLW PP ...
Страница 40: ... ZRNQFGF 8KGYU CPF 2CTVU KUV SORGHG 9LHZV DQG 3DUWV LVW QGRRU 8QLW 0RGHOV 5 1 5 1 5 1 ...
Страница 42: ... ZRNQFGF 8KGYU CPF 2CTVU KUV 0RGHO 5 1 ...
Страница 50: ... ZRNQFGF 8KGYU CPF 2CTVU KUV 2XWGRRU 8QLW 0RGHO 5 1 2 ...
Страница 52: ... ZRNQFGF 8KGYU CPF 2CTVU KUV 0RGHO 5 1 2 ...
Страница 55: ...6TQWDNGUJQQVKPI 0RGHO 0RGHO ...
Страница 85: ...4GOQXCN 2TQEGFWTG 2 Remove the chassis sub assy and condenser sub assy condenser sub assy chassis sub assy ...