1.Mounting plate should be installed horizontally. As the water tray's outlet for the indoor unit is two-way type, during
installation, the indoor unit should slightly slant to water tray's outlet for smooth drainage of condensate.
2.Fix the mounting plate on the wall with screws.
3.Be sure that the mounting plate has been fixed firmly enough to withstand about 60 kg. Meanwhile, the weight should be
evenly shared by each screw.(Unit:mm)
7.3.1 Installation of Mounting Plate
1.Slant the piping hole (Φ55 or Φ70) on the wall slightly downward to the outdoor side.
2.Insert the piping-hole sleeve into the hole to prevent the connection piping and wiring
from being damaged when passing through the hole.
1.Connect the drain hose to the outlet pipe of the indoor unit.Bind the joint with
rubber belt.
2.Put the drain hose into insulating tube.
3.Wrap the insulating tube with wide rubber belt from the joint of outlet pipe and
insulating pipe so as to prevent shift of insulating tube. The drain hose should be
placed at a downward slant for easy discharge of condensate.
Note: the insulating tube should be connected reliably with the sleve outside the
outlet pipe. The drain hose should be downward slant, without distortion, bulge or
fluctuation. Do not put the water outlet in the water.
1.Open the front panel.
2.Remove the wiring cover.Connect and fix power connection cord to
the terminal board as shown in Fig 2.
3.Make the power connection cord through the hole in the back of
indoor unit.
4.Reinstall the cord anchorage and wiring cover.
5.Reinstall the front panel.
7.3.2 Drill Piping Hole
7.3.3 Installation of Drain Hose
7.3.4 Connecting Indoor and Outdoor Electric Wires
Fig.2
Wall
Wall
Mark on the middle of it
Gradienter
(Rear piping hole)
(Rear piping hole)
Space
to the
wall
150mm
above
Space
to the
wall
150mm
above
BU
BK
BN
YEGN
Wiring Cover
Outdoor unit connection
3
2
BU
BK
BN
YEGN
Outdoor unit connection
3
2
Model:18K
Model:24K
Wall
Wall
Mark on the middle of it
Gradienter
(Rear piping hole)
(Rear piping hole)
Space
to the
wall
150mm
above
Space
to the
wall
150mm
above
18K
24K
Above 150mm from
the celling
Above 150mm from
the celling
Φ55
Φ55
Φ70
Φ70
,QVWDOO,QGRRU8QLW
Содержание GWH18RC-K3DNA1A
Страница 15: ... QPUVTWEVKQP 8KGYU RQVWUXFWLRQ 9LHZV QGRRU 8QLW ĭ ĭ 0RGHO 8QLW PP ĭ ĭ ...
Страница 16: ... QPUVTWEVKQP 8KGYU 2XWGRRU 8QLW 8QLW PP ...
Страница 40: ... ZRNQFGF 8KGYU CPF 2CTVU KUV SORGHG 9LHZV DQG 3DUWV LVW QGRRU 8QLW 0RGHOV 5 1 5 1 5 1 ...
Страница 42: ... ZRNQFGF 8KGYU CPF 2CTVU KUV 0RGHO 5 1 ...
Страница 50: ... ZRNQFGF 8KGYU CPF 2CTVU KUV 2XWGRRU 8QLW 0RGHO 5 1 2 ...
Страница 52: ... ZRNQFGF 8KGYU CPF 2CTVU KUV 0RGHO 5 1 2 ...
Страница 55: ...6TQWDNGUJQQVKPI 0RGHO 0RGHO ...
Страница 85: ...4GOQXCN 2TQEGFWTG 2 Remove the chassis sub assy and condenser sub assy condenser sub assy chassis sub assy ...