DC Inverter U-match Series Duct Type Unit
32
3.2.6 Installation of Drain Pipe
(1) It is not allowed to connect the condensate drain pipe into waste pipe or
other pipelines which are likely to produce corrosive or peculiar smell to
prevent the smell from entering indoors or corrupt the unit.
(2) It is not allowed to connect the condensate drain pipe into rain pipe to
prevent rain water from pouring in and cause property loss or personal
injury.
(3) Condensate drain pipe should be connected into special drain system for
air conditioner.
3.2.6.1 Indoor Side Drain Pipe
NOTE!
Install the drain hose in accordance with the instructions in this installation manual
and keep the area warm enough to prevent condensation. Problems with the
piping may lead to water leaks.
(1) Install the drain hose with downward gradient (1/100 to 1/50) and no
risers or traps are used for the hose. See the following figure.
(2) Be sure there is no crack or leak on the drain hose to avoid the formation
of air pocket. See the following figure.
(3) When the hose is long, install supporters. See the following figure.
(4) Always use the drain hose which has been insulated properly.
(5) Use a suitable drain hose.
Содержание GUD100PH/A-T
Страница 22: ...DC Inverter U match Series Duct Type Unit 18 4 When outdoor units are installed one above another Unit mm...
Страница 58: ...DC Inverter U match Series Duct Type Unit 54 B Wire routing of unified power supply for single phase...
Страница 60: ...DC Inverter U match Series Duct Type Unit 56 Only for GUD160W NhA X...
Страница 61: ...DC Inverter U match Series Duct Type Unit 57 B Wire routing of unified power supply for three phase...
Страница 62: ...DC Inverter U match Series Duct Type Unit 58 Only for GUD160W NhA X...
Страница 78: ......