DC Inverter U-match Series Duct Type Unit
33
(6) There is a drain port on both the left and right sides. Select the drain port
to match the local conditions. See the following figure.
(7) When the unit is shipped from the factory, the drain port is defaulted to be
the one on the left side (electric box side).
(8) When using the drain port on the right side of the unit, reinstall the drain
cap to the left side drain port. See the following figure.
(9) Be sure to insulate where the drain port and the drain hose is connected.
See the following figure.
(10) The unused drain port also should be insulated properly. See the
following figure.
(11) There is adhesive on one side of the insulation so that after removing the
protective paper over it the insulation can be directly attached to the drain
hose.