DC Inverter U-match Series Duct Type Unit
7
3 Installation
3.1 Installation Preparation
3.1.1 Notice on Installation
(1) Notice on Refrigerant Concentration before Installation.
This air conditioner uses R32 refrigerant. The construction area for installation,
operation and storage of the air conditioner must be larger than the minimum
construction area. The minimum area for installation is determined by:
1) Refrigerant charging quantity for the entire system (ex-factory
charging qu additional charging quantity).
2) Checking out in the applicable tables:
A. For indoor unit, confirm the model of indoor unit and check the
corresponding table.
B. For outdoor unit that is installed or placed indoors, select the
corresponding table according to the height of the room.
Height of the room
Select the applicable table
<
1.8m
Floor standing type
≥1.8m
Wall mounted type
3) Refer to the following table to check out the minimum construction
area
Ceiling type
Wall mounted type
Floor standing type
Weight(kg)
Area (m
2
)
Weight(kg)
Area (m
2
)
Weight (kg)
Area (m
2
)
<
1.224
—
<
1.224
—
<
1.224
—
1.224
0.956
1.224
1.43
1.224
12.9
1.4
1.25
1.4
1.87
1.4
16.8
1.6
1.63
1.6
2.44
1.6
22.0
1.8
2.07
1.8
3.09
1.8
27.8
2.0
2.55
2.0
3.81
2.0
34.3
2.2
3.09
2.2
4.61
2.2
41.5
2.4
3.68
2.4
5.49
2.4
49.4
2.6
4.31
2.6
6.44
2.6
58.0
2.8
5.00
2.8
7.47
2.8
67.3
3.0
5.74
3.0
8.58
3.0
77.2
Содержание GUD100PH/A-T
Страница 22: ...DC Inverter U match Series Duct Type Unit 18 4 When outdoor units are installed one above another Unit mm...
Страница 58: ...DC Inverter U match Series Duct Type Unit 54 B Wire routing of unified power supply for single phase...
Страница 60: ...DC Inverter U match Series Duct Type Unit 56 Only for GUD160W NhA X...
Страница 61: ...DC Inverter U match Series Duct Type Unit 57 B Wire routing of unified power supply for three phase...
Страница 62: ...DC Inverter U match Series Duct Type Unit 58 Only for GUD160W NhA X...
Страница 78: ......