Gree GMV6 DC Inverter VRF Units Service Manual
51
Press the SW4 back button on the master module to return to the previous process or exit the function
setting status.
The default status is 00, that is, no silence.
4.2.3.4 A8 After-Sales Vacuum Pumping Mode
Introduction:
This function is used to ensure the vacuum of the entire system during maintenance and to avoid
dead pipeline zones. When this function is set, both the expansion valve and the solenoid valve of the
unit will open.
Setting steps:
Step 1:
Enter A8 after-sales vacuum pumping mode, and ensure that the master module displays
as follows:
LED1
LED2
LED3
Function code
Display status
Current process
Display status
Current status
Display status
A8
On
00
Blinks
OC
Blinks
The system enters the to-be-confirmed status of vacuum pumping mode.
Step 2:
Press the SW3 button. The system enters the confirmed status of vacuum pumping mode
and all modules display as follows:
LED1
LED2
LED3
Function code
Display status
Current process
Display status
Current status
Display status
A8
On
00
On
OC
On
At this time, the expansion valves of all indoor and outdoor units are open, and the entire system
cannot be started.
When you press the SW4 back button on the master unit for over 5 seconds or the vacuum pumping
status remains for 24 hours, the entire system exits the status.
4.2.3.5 n0 Auto Energy Saving
Introduction:
This function sets the user-required energy saving mode. The default mode is capability priority
control.
After energy saving mode is set, the system capability will deteriorate.
Code
Function Name
01
Capability priority control (default setting)
02
Energy saving priority control
Setting steps:
Step 1:
Enter n0 system energy saving operation, and ensure that the master unit displays as follows:
LED1
LED2
LED3
Function code
Display status
Current
process/mode
Display status
Current status
Display status
n0
On
01
Blinks
OC
Blinks
Step 2:
Press the SW1 up button and the SW2 down button to select the corresponding mode.