Gree GMV6 DC Inverter VRF Units Service Manual
27
—
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Cod
e
Display
status
12_reserved function
db
ON
12
ON
01
ON
—
Step 16:
After the unit debugging method is confirmed, the system automatically selects cooling or
heating mode according to the ambient temperature.
Once cooling/heating mode is selected, the relevant display is as below.
—
Debugging
code
Progress code
Status code
Meaning
Progress
LED1 LED2 LED3 LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
13~15_ pilot
run stage
db
ON
13/14/1
5
ON
AC
ON
Pilot run of cooling mode
db
ON
13/14/1
5
ON
AH
ON
Pilot run of heating mode
db
ON
13/14/1
5
ON
Correspo
nding
error
code
ON
There’s fault on pilot run stage.
Note: fault module display
db
ON
13/14/1
5
ON
J0
ON
There’s fault on pilot run stage.
Note: non-fault module display
db
ON
13/14/1
5
ON
U9
ON
Outdoor unit’s pipeline or valve is abnormal.
db
ON
13/14/1
5
ON XXXX/U8
ON
The system detected the indoor unit’s pipeline
is abnormal. XXXX indicates engineering
number of fault indoor unit. 2s later, U8 fault
occurred for No. 100 indoor unit. LED3 will
display as below: 01 (2s later) 00 (2s later) U8,
and it will display like that circularly.
Note:
In the pilot run stage, the unit will display corresponding procedures according to actual
circumstances.
Once debugging is completed, resume the standby status and the display is as below:
Debugging code
Progress code
Status code
Meaning
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
01~04
ON
OF
ON
OF
ON
The complete unit has finished the
debugging and it stays at standby
status. LED1 displays module
address; LED2 and LED3 displays
“OF”.
Once the debugging for the complete unit is finished, please set relevant functions for the unit
according to the actual functional requirements of the project. Refer to relative technical materials for the
detailed operation method. If there is no special requirement, skip this step directly.
When delivery it to the user for operation, explain the precautions to the user.