Gree GMV6 DC Inverter VRF Units Service Manual
58
LED1
LED2
LED3
Description
Module address
Module
failure/indoor unit
failure
Module status
ADD
C9
ON
System running-fan emergency operation
status
ADD
C9
OF
System standby-fan emergency operation
status
NOTES!
①
This function is applicable only to dual-fan models;
②
A module can set only one fan to emergency mode;
③
The default status is 00.
④
The system cannot run continuously for more than 120 hours in fan emergency operation
status. If it exceeds 120 hours, the entire system is stopped, and the indoor unit displays the
"Ad" limit operation code.
4.2.3.13 CA Module Failure Emergency Operation
This function is after-sales emergency setting when a module works abnormally. It shields the
abnormal module in a short time to ensure the emergency operation of other modules.
Setting steps:
Enter the function setting on the main board of the faulty basic module. The module displays as
follows:
LED1
LED2
LED3
Function code
Display status
Current process
Display status
Current status
Display status
CA
On
00
Blinks
OC
Blinks
Press the SW1 up button and the SW2 down button to select the corresponding module to enter and
exit emergency operation status.
LED1
LED2
LED3
Description
Function
code
Display
status
Current
process
Display
status
Current
status
Display
status
CA
On
00
Blinks
OC
Blinks
All basic modules run normally.
CA
On
01
Blinks
OC
Blinks
The operation of module 1 is
shielded.
CA
On
02
Blinks
OC
Blinks
The operation of module 2 is
shielded.
CA
On
03
Blinks
OC
Blinks
The operation of module 3 is
shielded.
CA
On
04
Blinks
OC
Blinks
The operation of module 4 is
shielded.
After selecting the corresponding value, press the SW3 confirm button. The shielded module displays
as follows:
LED1
LED2
LED3
Function code
Display status
Mode
Display status
Current status
Display status
CA
On
00
On
OC
On
CA
On
01
On
OC
On