ERV+DX coil
21
personal injury.
3) he condensate drainage pipe must be connected to the drainage system
specialized for the air conditioner.
4) The shorter the drainage pipe, the better it is. Keep it downward with an
inclination of 1°
~
2° or more so that the condensate can be easily drained
away.
5) Apply thermal insulation for the drainage pipe. The insulation cotton used for
thermal insulation of the drainage pipe is already provided in the package of
accessories.
Figure 3-8 Thermal insulation of drain pipes
6) If the drainage pipe is used for several appliances, the location of the
drainage pipe should be 100mm lower than the drainage port of each
appliance. In this case, use a thicker pipe.
7) Drain pipes are hard PVC types which can be bought locally. When
connecting the pipes, insert the end of the PVC pipe into the drainage port
and then use drainage hose and wire tie to tie them well. Do not use glue to
fasten the drainage port and drainage hose.
(2) Installation of Drainage Pipe
1) Insert the drainage hose into the drainage port and tie them with adhesive
tape, as shown below.
2) Twist on the pipe clamp. The distance between the nut and the hose is less
than 4mm.