ERV+DX coil
13
(10) The circuit breaker should have both magnetic trip and thermal trip functions so
as to protect the unit when short circuit or overload occurs.
3.2.2 Requirements for Electric Installation
(1) Reliable grounding must be ensured. The yellow-green wire inside the unit is a
ground wire, so it shall not be used for other purposes nor shall it be cut. Do not
tighten it with tapping screws; otherwise it will cause risk of electric shock.
(2) Power supply must provide reliable grounding terminal. Do not connect the
ground wire to the following:
1. Water pipe; 2. Gas pipe; 3. Drain pipe; 4. Other places that are deemed as not
reliable by professional personnel.
WARNING!
Before installation and maintenance, please cut off power supply to avoid electric shock.
Please use the wire according to related configuration requirement. Otherwise it may lead to
unit malfunction and hazards such as electric shock and fire hazard.
Special statement
If the users alter the electric control system by themselves without prior consent of our
company, our company will not bear any responsibility for the abnormal results caused by
this.
3.2.3 Requirements for Electric Installation
Dimension of power cord and capacity of air switch:
Table 3-1 Wiring requirement
Model
Power
specification
Circuit breaker
capacity (A)
Wire diameter (mm²)
Ground wire Ground wire
GMV-VDR5PH/SA-S
220–240V
~
50/60Hz
6
3x1.0
3x1.0
GMV-VDR8PH/SA-S
GMV-VDR10PH/SA-S
NOTES!
(1) Selection of circuit breaker and power cord in the above table is based upon
unit’s maximum power (maximum current).
(2) Specification of power cord is based on the working condition where ambient
temperature is 40
℃
and multi-core copper cable (working temperature is 90
℃
,