background image

 

 

Exception Clauses 

Manufacturer will bear no responsibilities when personal injury or property loss is caused 

by the following reasons: 

(1)  Damage the product due to improper use or misuse of the product; 
(2)  Alter, change, maintain or use the product with other equipment without abiding by the 

instruction manual of manufacturer; 

(3)  After verification, the defect of product is directly caused by corrosive gas; 
(4)  After verification, defects are due to improper operation during transportation of 

product; 

(5)  Operate, repair, maintain the unit without abiding by instruction manual or related 

regulations; 

(6)  After verification, the problem or dispute is caused by the quality specification or 

performance of parts and components that produced by other manufacturers; 

(7)  The damage is caused by natural calamities, bad using environment or force majeure. 

 

Содержание GMV-ND100G/B4B-T

Страница 1: ...MV ND50G C2B T GMV ND36G B4B T GMV ND45G B6B T GMV ND56G C2B T GMV ND45G B4B T GMV ND50G B6B T GMV ND63G C2B T GMV ND50G B4B T GMV ND56G B6B T GMV ND71G C2B T GMV ND56G B4B T GMV ND63G B6B T GMV ND22G...

Страница 2: ...used for long cut off the power supply please energize and preheat the unit in advance before reusing it 3 Please properly select the model according to actual using environment otherwise it may impac...

Страница 3: ...turer 3 After verification the defect of product is directly caused by corrosive gas 4 After verification defects are due to improper operation during transportation of product 5 Operate repair mainta...

Страница 4: ...nect Cables and Terminals of Wiring Board 11 5 2 Power Cord Connection 12 5 3 Connection of Communication Line of IDU and ODU 12 5 4 Connection of Communication Line of Wired Controller 13 5 5 Illumin...

Страница 5: ...interface shall comply with electrical security requirement voltage shall be 220 240V 50Hz or 208 230V 60Hz current shall be referred to the table of Wiring Requirements in Section 3 4 and safety cla...

Страница 6: ...special accessories and parts for installation to prevent water leakage electric shock and fire hazard etc If refrigerant leakage happens please ventilate the room immediately Diameter of power cord...

Страница 7: ...onditioner can be cleaned only when it has been turned off and the power has been cut off otherwise it may cause electric shock or injury Never spray or flush water towards the air conditioner otherwi...

Страница 8: ...pointed service center for help Any personal injury or property loss caused by improper installation improper debug unnecessary repair or not following the instructions of this manual should not be th...

Страница 9: ...Please contact the local Gree appointed service center before installation Any malfunctioncaused by the unit that is not installed by the Gree appointed service center would probably not be dealt wit...

Страница 10: ...it 3 3 1 Select communication line for indoor unit and wired controller Fig 3 2 Material type Total length of communication line between indoor unit and wired controller L m feet Wire size mm2 AWG Mat...

Страница 11: ...D28G B4B T GMV ND36G B4B T GMV ND45G B4B T GMV ND50G B4B T GMV ND56G B4B T GMV ND63G B4B T GMV ND71G B4B T GMV ND80G B4B T GMV ND90G B4B T GMV ND100G B4B T 220 240V 50Hz 208 230V 60Hz 6 1 1 GMV ND22G...

Страница 12: ...22G B6B T GMV ND28G B6B T GMV ND36G B6B T GMV ND15G B4B T GMV ND18G B4B T GMV ND22G B4B T GMV ND28G B4B T GMV ND36G B4B T GMV ND22G C4B T GMV ND28G C4B T GMV ND36G C4B T GMV ND22G C2B T GMV ND28G C2B...

Страница 13: ...r side The center of the hole should be determined referring to Fig 4 2 2 Insert the piping hole sleeve into the hole to prevent the connected piping and wiring from being damaged when passing through...

Страница 14: ...ction pipe with two leading pipes and then tighten the joint nuts tightly Connect the connect pipe with the two relative leading pipe tie the nut on tie in of the connect pipe tightly NOTES Be careful...

Страница 15: ...unication wires should be separated from power cord and connection wire between indoor unit and outdoor unit Adjust the static pressure via wired controller according to site circumstance 5 1 Connect...

Страница 16: ...gent or similarly qualified persons in order to avoid a hazard That the appliance shall be installed in accordance with national wiring regulations This appliance incorporates an earth connection for...

Страница 17: ...be connected in parallel between terminal screw D1 and D2 as shown in Fig 5 5 5 4 Connection of Communication Line of Wired Controller 1 Open the cover of electric box of indoor unit 2 Lead the commun...

Страница 18: ...f the unit Shown in Fig 5 6 1 Cut down tailings 1 when only the power cord is led 2 Cut down tailings 1 2 or 1 2 3 when the connection cord and wire are led 3 The piping types are recommended 2 Let th...

Страница 19: ...e operating status of the indoor unit the power will be turned on and when there is no condensed water the power will be turned off Main board terminal CN35 It s used to detect the water overflow erro...

Страница 20: ...Multi Variable Air Conditioners Wall Mounted Type Indoor Unit 16 Fig 5 7 6 The Best Usage Method Fig 6 1 1 Adjust to proper indoor temperature too cool of indoor temperature is not good for health...

Страница 21: ...indoor and outdoor temperatures within 5 C 4 The better effect will be maintained by adjusting the guide louver downward for heating and horizontal for cooling 5 When the air conditioner is running do...

Страница 22: ...Clean the panel Clean it with a soft hair brush water and neutral cleaning fluid and then dry it CAUTION Do not use water above 45 C to wash the panel to prevent decoloration or deformation Install th...

Страница 23: ...ason 1 Clean filter and body of air conditioner 2 Cut off the main power supply of air conditioner 8 Table of Error Codes for Indoor Unit Error Code Content Error Code Content Error Code Content L0 In...

Страница 24: ...ER had been set on the wireless remote controller The cooling heating effect of the air conditioner was not good Is the temperature set properly Is the inlet outlet vent of the outdoor unit blocked Is...

Страница 25: ...te controller can make the guide louver swing up and down or makes the guide louver stop at a certain angle to have air supplied 2 Press the SWING button on the wireless remote controller to make the...

Страница 26: ......

Отзывы: