Multi Variable Air Conditioners Wall Mounted Type Indoor Unit
15
GMV-ND36G/C4B-T,GMV-ND36G/C2B-T,GMV-ND36G/D2B-T,GMV-ND45G/B6B-T,
GMV-ND45G/B4B-T,GMV-ND45G/C4B-T,GMV-ND45G/C2B-T,GMV-ND45G/D2B-T,
GMV-ND50G/B6B-T,GMV-ND50G/B4B-T,GMV-ND50G/C4B-T,GMV-ND50G/C2B-T,
GMV-ND50G/D2B-T,GMV-ND56G/B6B-T,GMV-ND56G/B4B-T,GMV-ND56G/C4B-T,
GMV-ND56G/C2B-T,GMV-ND56G/D2B-T,GMV-ND63G/B6B-T,GMV-ND63G/B4B-T,
GMV-ND63G/C4B-T,GMV-ND63G/C2B-T,GMV-ND63G/D2B-T,GMV-ND71G/B6B-T,
GMV-ND71G/B4B-T,GMV-ND71G/C4B-T,GMV-ND71G/C2B-T,GMV-ND71G/D2B-T.
The external water pump is purchased by the user, and the water pump is selected
according to the requirements. The installation must be carried out by a professional according
to the local laws and regulations and the pump manual.
Main board terminal CN8: Provide power for the external water pump
;
power specification:
220-240V~50Hz,208-
230V~60Hz; Power of water pump ≤30W; when there may be condensed
water according to the operating status of the indoor unit, the power will be turned on, and
when there is no condensed water, the power will be turned off.
Main board terminal CN35: It’s used to detect the water overflow error signal. When the
terminal CN35 is continuously disconnected for a certain period of time, the error code L3 of
water overflow error will be displayed on the indoor unit and the unit stops operation; when the
terminal CN35 is continuously connected for a period of time, the water overflow error will be
eliminated. When the user doesn’t need to use this function, the terminal CN35 shall be
connected according to the short circuit connection at the time of ex-factory.
Connection of external water pump and indoor unit
(1) Remove the panel.
(2) Remove the electric box cover.
(3) Connect the power cord of external water pump to the positions L and N of terminal
CN8 of the main board; connect the alarm wire to the positions 1 and 2 of terminal
CN35 (refer to Fig .5.7).
(4) Take out the wiring clip from the package of accessories. Remove the original wiring
clip from the electric box and secure the power cord and alerter wire with the new
clip.