(8) Failure start-up.
Failure start-up for
consecutive 6
times
Work normally after
replacing main board?
Replace compressor and
liquid gas separator
YES
NO
Work normally
(9) Reset protection for drive module of compressor, drive PFC protection for compressor,
malfunction of drive temperature sensor for compressor, circuit malfunction of drive
current detection for compressor.
(10) Drive IPM overtemperature protection for compressor.