Gree GMV MTAC VRF for North America
63
No.
Installation Problem
Possible Consequence
9
The refrigerant pipe leaks.
Insufficient refrigerant circulating in the system decreases the
cooling performance of the air conditioner. Long-term operation
under such circumstance may cause an overheating compressor or
even damage the compressor.
10
Water drainage from the condensate
water pipe is not smooth.
Residual water in IDUs can affect the normal operation of the
system. The possible water leakage can damage the IDU's
decoration.
11
The ratio of slop for condensate water
pipe is insufficient or the condensate
water pipe is incorrectly connected.
Reverse slop or inconsistent connection of condensate water pipe
can hinder the smooth drainage and cause leakage of the IDU.
12
The air channel is improperly fixed.
The air channel will deform; vibration and noise occur during unit
operating.
13
The guide vane of air channel is not
reasonably manufactured.
Uneven air quantity allocation reduces the overall performance of
the air conditioner.
14
The refrigerant pipe or condensate
water pipe does not meet the insulation
requirement.
Water can easily condensate and drip to damage the indoor
decoration, or even trigger the protection mode of system due to
overheating operation.
15
The installation space for IDU is
insufficient.
Since there is a lack of space for maintenance and checking, indoor
decoration might need to be damaged during such operation.
16
The IDU or the location of the air outlet
or return air inlet is not designed
reasonably.
The air outlet or return air inlet may be short-circuited, thus
affecting the air conditioning performance.
17
The ODU is improperly installed.
The ODU is difficult to be maintained; unit exhaust is not smooth,
which reduces the heat exchanging performance or even prevent
the system from normal operation; in addition, the cold and hot air
for heat exchange and the noise may annoy people in surrounding
areas.
18
Power cables are incorrectly provided. Unit components may be damaged and potential safety hazard
may occur.
19
Control communication cables are
incorrectly provided or improperly
connected.
The normal communication in the system fails or the control over
IDUs and ODUs turn in a mess.
20
Control communication cables are not
properly protected.
The communication cables are short-circuited or disconnected, and
the unit cannot be started up due to communication failure.
Understand the special requirement (if any) for unit installation before implementation to
ensure installation quality. Relevant installers must have corresponding engineering construction
qualifications.
Special type operators involved in the engineering implementation, such as welders,
electricians, and refrigeration mechanics must have relevant operating licenses and are
accredited with vocational qualification certification.
2 Installation Materials Selection
The materials, equipment and instruments used during air conditioning engineering
construction must have certifications and test reports. Products with fireproof requirements must
be provided with fireproof inspection certificates and must meet national and relevant compulsory
standards. If environmentally-friendly materials are to be used as required by customers, all such
materials must meet national environmental protection requirement and be provided with relevant
certificates.
Содержание GMV MTAC VRF Series
Страница 1: ...GMV MTAC VRF for North America GC201908 I Capacity 12kBtu h Rated Frequency 60 Hz...
Страница 5: ...Gree GMV MTAC VRF for North America 1 PRODUCT...
Страница 11: ...Gree GMV MTAC VRF for North America 7 CONTROL...
Страница 36: ...Gree GMV MTAC VRF for North America 32 Installation is in progress Click Close to complete the installation...
Страница 43: ...Gree GMV MTAC VRF for North America 39 Select language Select system of units...
Страница 64: ...Gree GMV MTAC VRF for North America 60 Switchover of Software Languages...
Страница 65: ...Gree GMV MTAC VRF for North America 61 INSTALLATION...
Страница 88: ...Gree GMV MTAC VRF for North America 84 MAINTENANCE...
Страница 117: ...JF00304109...