DC Inverter Side Discharge VRF
Ⅱ
for North America
68
2.4 Communication cable and control cable
Note: For air conditioning units installed in places with strong electromagnetic
interference, shielded wire must be used as the communication cables of the IDU and
wired controller, and shielded twisted pairs must be used as the communication cables
between IDUs and between the IDU and ODU.
Communication cable selection for ODU and IDUs
Material Type
Total Length of
Communication Cable
between IDU Unit and
IDU (ODU ) Unit L(m/feet)
Wire size
Remarks
Light/Ordinary
polyvinyl chloride
sheathed cord.
L
≤
1000(3280-5/6)
≥2×AWG18
1) If the wire diameter is enlarged
to 2×AWG16, the total
communication line length can
reach 1500 m (4921-1/4feet).
2) The cord shall be Circular cord
(the cores shall be twisted
together).
3) If unit is installed in places with
intense magnetic field or strong
interference, it is necessary to
use shielded wire.
2.5 Power cable
Only copper conductors can be used as power cables. The copper conductors must
meet relevant national standard and satisfy the carrying capacity of unit.
2.6 Hanger rod and support
(1)
Hanger rod: M8 or M10;
(2)
U-steel: 14# or above;
(3)
Angle steel: 30mm×30mm×3mm or above;
(4)
Round steel:
Φ10mm or above
3 Installation of outdoor unit
3.1 Check before installation
(1)
Before installation, please check the power cord if it complies with the power supply
requirement on the nameplate. Make sure the power supply is safe.
(2)
This air conditioner must be properly grounded through the receptacle to avoid
electric shock. The ground wire shouldn’t be connected with gas pipe, water pipe,
lightning arrester or telephone line.
(3)
Maintain good air circulation to avoid lacking oxygen.
(4)
Read this manual carefully before installation.
3.2 Selection of installation site
(1)
Select a location which is strong enough to hold unit’s weight so that unit can stand
still and erect.
Содержание GMV-36WL/A-T(U)
Страница 1: ...DC INVERTER SIDE DISCHARGE VRF Ⅱ FOR NORTH AMERICA ...
Страница 3: ...DC Inverter Side Discharge VRF Ⅱ for North America 1 PRODUCT ...
Страница 10: ...DC Inverter Side Discharge VRF Ⅱ for North America 8 CONTROL ...
Страница 15: ...DC Inverter Side Discharge VRF Ⅱ for North America 13 ...
Страница 16: ...DC Inverter Side Discharge VRF Ⅱ for North America 14 Button Graphics ...
Страница 24: ...DC Inverter Side Discharge VRF Ⅱ for North America 22 4 3 2 2 Appearance ...
Страница 30: ...DC Inverter Side Discharge VRF Ⅱ for North America 28 Installation is in progress ...
Страница 33: ...DC Inverter Side Discharge VRF Ⅱ for North America 31 Installation is in progress ...
Страница 35: ...DC Inverter Side Discharge VRF Ⅱ for North America 33 Click Next ...
Страница 65: ...DC Inverter Side Discharge VRF Ⅱ for North America 63 Switchover of Software Languages ...
Страница 66: ...DC Inverter Side Discharge VRF Ⅱ for North America 64 INSTALLATION ...
Страница 94: ...DC Inverter Side Discharge VRF Ⅱ for North America 92 MAINTENANCE ...
Страница 109: ...DC Inverter Side Discharge VRF Ⅱ for North America 107 3 3 Circuit diagram GMV 36WL A T U GMV 48WL A T U GMV 60WL A T U ...
Страница 131: ...JF00302320 ...