DC Inverter Side Discharge VRF
Ⅱ
for North America
76
6.1.2 Indoor Pipe Connection
(1)
Remove pipe cover and pipe plug.
(2)
Direct the flared part of copper pipe to the center of screwed joint. Twist on the flared
nut tightly by hand, as in Fig. 13. (Make sure indoor pipe is correctly connected.
Improper location of the center will prevent flared nut from being securely twisted.
Thread of nut will get damaged if the flared nut is twisted forcibly.)
(3)
Use torque wrench to twist on the flared nut tightly until the wrench gives out a click
sound. (Hold the handle of wrench and make it at right angle to the pipe. as in Fig. 14
(1)
Use sponge to wrap the un-insulated connection pipe and joint. Then tie the sponge tightly with
plastic tape.
(2)
Connection pipe should be supported by a bearer rather than the unit.
(3)
The bending angle of piping should not be too small; otherwise the piping might have cracks.
Please use a pipe bender to bend the pipe.
(4)
When connecting IDU with connection pipe, do not pull the big and small joints of IDU with force in
case the capillary tube or other tubes have cracks and cause leakage.
Fig. 13 Fig. 14
Pipe Diameter
Tightening Torque
6mm(1/4inch)
15-30N·
m(11-22ft.-1b.)
9.5mm(3/8 inch)
35-40N·
m(26-29ft.-1b.)
12.7mm(1/2 inch)
45-50N·
m(33-37ft.-1b.)
16mm(5/8 inch)
60-65N·
m(44-48ft.-1b.)
19.05mm(3/4 inch)
70-75N·
m(52-55ft.-1b.)
6.1.3 Outdoor Pipe Connection
(
1
)
Pipe connection for GMV-36WL/A-T(U)
、
GMV-48WL/A-T(U)
Twist the flared nut on the connection pipe of outdoor valves. Twisting method is the
same as for indoor pipe connection.
According to customer requirement or space limit, outlet pipe can be installed from
the front, right or rear side.
Содержание GMV-36WL/A-T(U)
Страница 1: ...DC INVERTER SIDE DISCHARGE VRF Ⅱ FOR NORTH AMERICA ...
Страница 3: ...DC Inverter Side Discharge VRF Ⅱ for North America 1 PRODUCT ...
Страница 10: ...DC Inverter Side Discharge VRF Ⅱ for North America 8 CONTROL ...
Страница 15: ...DC Inverter Side Discharge VRF Ⅱ for North America 13 ...
Страница 16: ...DC Inverter Side Discharge VRF Ⅱ for North America 14 Button Graphics ...
Страница 24: ...DC Inverter Side Discharge VRF Ⅱ for North America 22 4 3 2 2 Appearance ...
Страница 30: ...DC Inverter Side Discharge VRF Ⅱ for North America 28 Installation is in progress ...
Страница 33: ...DC Inverter Side Discharge VRF Ⅱ for North America 31 Installation is in progress ...
Страница 35: ...DC Inverter Side Discharge VRF Ⅱ for North America 33 Click Next ...
Страница 65: ...DC Inverter Side Discharge VRF Ⅱ for North America 63 Switchover of Software Languages ...
Страница 66: ...DC Inverter Side Discharge VRF Ⅱ for North America 64 INSTALLATION ...
Страница 94: ...DC Inverter Side Discharge VRF Ⅱ for North America 92 MAINTENANCE ...
Страница 109: ...DC Inverter Side Discharge VRF Ⅱ for North America 107 3 3 Circuit diagram GMV 36WL A T U GMV 48WL A T U GMV 60WL A T U ...
Страница 131: ...JF00302320 ...