DC Inverter Side Discharge VRF
Ⅱ
for North America
123
(3)
Calculation example
IDU:
No.
IDU
①
IDU
②
IDU
③
IDU
④
Model
Duct type
GMV-ND18PLS/A-T(U)
Duct type
GMV-ND12PLS/A-T(U)
Duct type
GMV-ND09PLS/A-T(U)
Duct type
GMV-ND09PLS/A-T(U)
Liquid pipe:
No.
A
B
C
D
Pipe size
Φ9.52mm
(
Φ3/8inch)
Φ9.52 mm
(
Φ3/8inch)
Φ9.52 mm
(
Φ3/8inch)
Φ6.35 mm
(
Φ1/4inch)
Length
10m
(32-3/4feet)
5m
(16-3/8feet)
5m
(16-3/8feet)
5m
(16-3/8feet)
No.
a
b
c
d
Pipe size
Φ9.52mm
(
Φ3/8inch)
Φ6.35 mm
(
Φ1/4inch)
Φ6.35 mm
(
Φ1/4inch)
Φ6.35 mm
(
Φ1/4inch)
Length
3m
(9-3/4feet)
3m
(9-3/4feet)
2m
(6-5/8feet)
1m
(3-1/4feet)
Total length of each liquid pipe
Φ9.52
:
A+B+C+a=10+5+5+3=23m(75-1/2 feet)
Φ6.35: D+b+c+d=5+3+2+1=11m(36feet)
NOTICE!
Liquid pipe that is within 20m(65-
5/8 feet) doesn’t need to be added with
refrigerant.
Therefore, the minimum quantity of additional refrigerant = (23-20)×0.054+11×0.022
=
0.404kg(14oz)
5.3.2 Operation procedure for adding refrigerant
(1)
Put the charging tank on the weightometer, record the reading and then calculate the data
after charging refrigerant;
(2)
Use charging conduct pipe to connect the double-ended manometer with governing valve
Содержание GMV-36WL/A-T(U)
Страница 1: ...DC INVERTER SIDE DISCHARGE VRF Ⅱ FOR NORTH AMERICA ...
Страница 3: ...DC Inverter Side Discharge VRF Ⅱ for North America 1 PRODUCT ...
Страница 10: ...DC Inverter Side Discharge VRF Ⅱ for North America 8 CONTROL ...
Страница 15: ...DC Inverter Side Discharge VRF Ⅱ for North America 13 ...
Страница 16: ...DC Inverter Side Discharge VRF Ⅱ for North America 14 Button Graphics ...
Страница 24: ...DC Inverter Side Discharge VRF Ⅱ for North America 22 4 3 2 2 Appearance ...
Страница 30: ...DC Inverter Side Discharge VRF Ⅱ for North America 28 Installation is in progress ...
Страница 33: ...DC Inverter Side Discharge VRF Ⅱ for North America 31 Installation is in progress ...
Страница 35: ...DC Inverter Side Discharge VRF Ⅱ for North America 33 Click Next ...
Страница 65: ...DC Inverter Side Discharge VRF Ⅱ for North America 63 Switchover of Software Languages ...
Страница 66: ...DC Inverter Side Discharge VRF Ⅱ for North America 64 INSTALLATION ...
Страница 94: ...DC Inverter Side Discharge VRF Ⅱ for North America 92 MAINTENANCE ...
Страница 109: ...DC Inverter Side Discharge VRF Ⅱ for North America 107 3 3 Circuit diagram GMV 36WL A T U GMV 48WL A T U GMV 60WL A T U ...
Страница 131: ...JF00302320 ...