28
Special functions
Caution
Caution
The indicated percentages are guide values that may vary to a greater or lesser extent
depending on the system, pump and pump stage.
The indicated percentages are guide values that may vary to a greater or lesser extent
depending on the system, pump and pump stage.. 100% is the maximum possible voltage/
frequency of the controller.
6.3.4. - max. speed
6.3.5. - min. speed
6.3.6. - Setpoint
The maximum speed of the pump is specifi ed here. During the setting the pump runs at the specifi ed speed
and the fl ow rate can be determined.
Settings range: 70% to 100% / Default setting: 100%
The minimum speed of the pump at relay R1 is specifi ed here. During the setting the pump runs at the
specifi ed speed and the fl ow rate can be determined.
Settings range: (Speed from „J.14.6. - Speed when „On““ on page 49) to max. speed -5% / Default
setting: 30%
This value is the control setpoint for Mode 3 (see „6.3.1. - Modes“ on page 27). If the value at the
collector sensor drops below this, the speed is reduced. If it rises above this, the speed is increased.
Settings range: 0° to 90°C / Default setting: 60°C