section 9: commissioning
Page 48
9.7 Parameters Input/output
The following parameter settings must be checked on commission
-
ing.
table 9-2:
Parameters input/output
level
Parameter
function description
Display and input value
remarks
Group
code
Default
Min.
max.
Unit
I
51 19
Terminal 19-18 : DHW remote contact
0=disable (Remote controller only)
1=enable
1
0
1
-
I
51 20
Terminal 20-21 : ON/OFF remote contact (CH)
Alarm input
0=disable
1=ON/OFF remote contact
1
0
1
-
ON/OFF by
Remote controller
0=enable
1=ON/disable
OFF/enable
2=enable
I
51 28
Terminal 28-29 : Night mode*
0=disable
1=enable
Refer to Section 8.6.
0
0
1
-
Parameter 5128
and Parameter
5130 are
synchronised in
same value
I
51 30
Terminal 30-31 : Low tariff*
0=disable
1=enable
Refer to Section 8.7.
0
0
1
-
I
51 46
Terminal 46 : DHW Electric heater or Backup heater
0=DHW Electric heater
1=Backup heater
0
0
1
-
* External timer required
For details of how to access the parameter settings, refer to Section 9.3.
9.8 remote controller Back light Display Parameters
The following parameters can be changed to adjust the back light
display.
table 9-3:
Back light display parameters
level
Parameter
function description
Display and input value
remarks
Group
code
Default
Min.
max.
Unit
U
02 03
Back light display at door open
0=OFF
1=ON
1
0
1
-
U
02 04
Time to turn off the back light display
60
10
300
10 sec
U
02 05
Time to back to normal display screen
120
10
300
10 sec
For details of how to access the parameter settings, refer to Section 9.3.