Page 89
Appendix D - Parameters List
Appendix D
Parameters List
Backlight display paramters
Level
Parameter
Function description
Display and input value
Remarks
Group
Code
Default
Min.
Max.
Unit
U
02 03
Back light display at door open
0=OFF
1=ON
1
0
1
-
U
02 04
Time to turn off the back light display
60
10
300
10 sec
U
02 05
Time to back to normal display screen
120
10
300
10 sec
Water temperature set points
Level
Parameter
Function description
Display and input value
Remarks
Group
Code
Default
Min.
Max.
Unit
I
21 00
Enable outgoing water set point
0=fixed set point
1=climatic curve
1
0
1
-
I
21 01
Fixed outgoing water set point
45.0
23.0
60.0
0.5°C
I
21 02
Maximum outgoing water temperature in Heating mode (Tm1)
45.0
23.0
60.0
0.5°C
I
21 03
Minimum outgoing water temperature in Heating mode (Tm2)
30.0
23.0
60.0
0.5°C
I
21 04
Minimum outdoor air temperature corresponding to maximum
outgoing water temperature (Te1)
-4
-20.0
50.0
0.5°C
I
21 05
Maximum outdoor air temperature corresponding to maximum
outgoing water temperature (Te2)
20.0
0.0
40.0
0.5°C
I
21 41
Hysteresis of water set point in heating
8.0
0.5
10.0
0.5°C
I
21 51
Low tariff deferential water set point for Heating
5.0
0.0
60.0
0.5°C
DHW (Domestic Hot Water)
Level
Parameter
Function description
Display and input value
Remarks
Group
Code
Default
Min.
Max.
Unit
I
31 01
DHW production priority setting
0=DHW is unavailable
1= DHW is available, and priority DHW over space heating
2= DHW is available, and priority space Heating over DHW
1
0
2
-
I
31 11
DHW Comfort set temperature
50.0
40.0
60.0
0.5°C
I
31 12
DHW Economy set temperature
40.0
30.0
50.0
0.5°C
I
31 21
Maximum time for DHW request
60
0
900
1 min
I
31 22
Minimum time for space heating
15
0
900
1 min
Heat pump unit
Level
Parameter
Function description
Display and input value
Remarks
Group
Code
Default
Min.
Max.
Unit
I
41 00
The heat pump turns ON/OFF based on
1=water set point
1
0
1
-
I
41 11
Maximum frequency of Night mode
80
50
100
5%
S
41 30
Maximum outgoing water set point in CH and DHW
55.0
23.0
60.0
0.5°c
Содержание Aerona 3 HPID10R32
Страница 5: ...Page 5 Page intentionally left blank ...
Страница 97: ...Page 97 Notes Notes ...
Страница 98: ...Notes Page 98 Notes ...
Страница 99: ...Page 99 Notes Notes ...