Section 6: Electrical
! NOTE !
Cable and circuit breakers should be to EN Standards.
Table 6-3:
Power supply cable and breaker capacity
Model
Power supply cable (mm²)
Breaker
capacity
Maximum
Minimum
HPID6R32
4.0
2.5
16A Class C
HPID10R32
4.0
2.5
20A Class C
HPID13R32
6.0
4.0
32A Class C
HPID17R32
6.0
4.0
32A Class C
! NOTE !
In the case of long cable runs, selection of correct cable
must be done in accordance with BS 7671 (IET Wiring
Regulations)
Strip ends of connecting cables in accordance with Figure 6-4.
Crimp terminals with insulating sleeves can be used if required
as illustrated in the diagram below for connecting the wires to the
terminal block. Stranded conductors shall not be soldered.
•
Use a circuit breaker with a 3 mm clearance of air gap between
the contacts.
•
Be sure to FULLY insert the cable cores into the proper
position of the terminal block.
•
Faulty wiring may cause not only abnormal operation but also
damage to PCB board.
•
Fasten each terminal screw securely.
•
To check the connections are secure, pull the cable slightly.
10 mm
30 mm
Terminal block
Crimp
terminal
Stripped wire :10mm
Sleeve
Crimp terminal
Sleeve
PCB(Terminal)
Figure 6-4:
Stripping the cables
! CAUTION !
It is important that the cable is stripped back 10mm.
If shorter, it is possible to clamp down onto the insulation.
If longer, a short circuit may occur.
Lockable
isolator
Consumer
unit
Figure 6-3:
Heat pump, isolator and consumer unit