Installation

311513D

7

Connecting the Electrical 
Control Panel to a Power Source

Have a trained electrician connect the electrical control 
panel (F

IG

. 3) to a grounded electrical source that has 

the required service ratings. See Table 1.

For information about specific terminal locations and 
connections, see the schematic drawing on page 17.

To connect the control panel to the electrical source:

1.

Locate the opening in the control panel`s top hous-
ing for the conduit that will enclose the wire from the 
facility's power source. The hole diameter is 0.804" 
(20 mm) and includes a cord strain relief for cable 
diameters from 0.236" (6 mm) to 0.472" (12 mm).

2.

Thread the wire from the power source into the con-
trol panel housing, and then connect the power 
source wires to the appropriate terminals on the 
panel.

F

IG

. 3. Electrical Control Panel

CAUTION

If power and grounding connections are not done 
properly, the equipment will be damaged and the war-
ranty will be voided. Check the label on the control 
box for the proper voltage.

Table 1: Electrical Specifications

Panel 

Voltage, 

Vac

Hz

Phase

Full Load 

Amps

220/240

50/60

1

15.5

TI8193b

Содержание 311208

Страница 1: ...2 Series A 400 F 204 C Maximum Control Temperature For complete system installation and operation instructions see the following manuals Important Safety Instructions Read all warnings and instruction...

Страница 2: ...m 6 Connecting the Electrical Control Panel to a Power Source 7 Check the Resistance Between the Supply Unit and the True Earth Ground 8 Checking Resistance 8 Resetting the Ground Fault Interrupt 10 E...

Страница 3: ...r in the work area ELECTRIC SHOCK HAZARD Improper grounding setup or usage of the system can cause electric shock Turn off and disconnect power at main switch before disconnecting any cables and befor...

Страница 4: ...cover The Therm O Flow Expansion Controls are intended to heat combinations of hot melt hoses and guns or acces sory devices Accessory devices include guns compen sators regulators manifolds and head...

Страница 5: ...eated Hose Zones 5 and 6 E Hose Hanger F Manual Dispense Valve G Extra Heated Hose Zone Acc 1 H Extra Dispense Valve Zone Acc 2 J 4 Zone Expansion Control K Electrical Control Panel 6 Zone L Heated Ra...

Страница 6: ...and accessories Dispensing Spray Gun Follow the dispensing spray gun grounding instructions Object Material is Applied To Ground the object according to your local code Material Drums Ground the mater...

Страница 7: ...duit that will enclose the wire from the facility s power source The hole diameter is 0 804 20 mm and includes a cord strain relief for cable diameters from 0 236 6 mm to 0 472 12 mm 2 Thread the wire...

Страница 8: ...dicated To check the sensor resistance 1 Make sure the power is off and that the disconnect switch is in the OFF position 2 Make electrical resistance checks for the compo nents 3 Replace any parts wh...

Страница 9: ...etting temperature con trols P I and d settings are preset for device types and will not need to be changed Refer to the Zone Setup Screens in your Therm O Flow manual for a list of device types and h...

Страница 10: ...onnect on the electrical control panel 2 Open the electrical control box and locate the Ground Fault Interrupt switch GFPE The ground fault interrupt will be in a neutral position between the ON and O...

Страница 11: ...fied in the Zone tab of the Setup screen while the unloader is in the Run state Sensor Error occurs in the following conditions When an enabled zone does not increase in temperature within 7 minutes w...

Страница 12: ...Electrical Control Panel Troubleshooting 12 311513D FIG 5 Electrical Schematic continued on page 13...

Страница 13: ...Electrical Control Panel Troubleshooting 311513D 13 FIG 6 Electrical Schematic continued...

Страница 14: ...IRE DUCT 1 25 X 3 0 WIRE DUCT SSR 113 SSR116 SSR 119 SSR 122 FU 113 FU 116 FU 119 FU 122 FU 1051 FU 1052 PCB 201 PS 123 GFPE 112 DC INT CONN 112 GND LUG N L TI8193b SSR113 SSR116 SSR119 SSR122 FU113 F...

Страница 15: ...ft 4 57 m long Runs between controller and heated hose 196314 16 pin to 16 pin Extension Cable 25 ft 7 62 m long Runs between controller and heated hose 196315 16 pin to 8 pin Extension Cable 15 ft 4...

Страница 16: ...Dimensions 16 311513D Dimensions Front View Side View 8 80 in 224 mm 14 50 in 368 mm 16 0 in 406 mm 14 50 in 368 mm 16 0 in 406 mm Four 0 40 in 11 mm diameter holes TI8166A TI8165A...

Страница 17: ...EATER CIRCUIT HOSE RTD SENSOR 108 2 ohms 1 ohm MACHINE END DH1 DH2 CONNECTOR PINOUT GUN END DH1 DH2 CONNECTOR PINOUT GUN HEATER GUN SENSOR NOT USED GUN SWITCH GUN GROUND HOSE CORE GROUND GND 16 Pin Ou...