POWER SOURCE

The GPS-iDETECT-P can be connected to either (I) house power source, or (II) GPS-iMOD power

supply. Please reference below the instructions for connecting to the target power source.

I. WIRING DIRECT TO HOUSE POWER SOURCE

1. Remove cable gland. Remove foam filler, but don’t discard. See FIGURE 2.

2. Use 300V 18/4 plenum-rated, SHIELDED cable rated for the voltage applied. Follow all

  local and national electric codes. Solid copper wiring is preferred.

3. The shield on the 18/4 cable should be grounded on one end, opposite the sensor. The

  shield on the 18/4 cable inside the sensor should not be connected to anything, including

 ground!

4. Connect power to the appropriate power input pins of the terminal block. See FIGURE 2.

  The neutral must be landed on the N terminal. If 240V, L2 is connected to N terminal.

5. Pull the cable through the gland. Place foam filler over the cable and then terminate to

  the circuit board. Push the board and foam spacer into the tube. Tighten the cable gland.

CONNECTION TO BMS/BAS

The detector is supplied with an alarm relay that can be wired into the building

management system. The internal relay has been provided with both normally open (NO)

and normally closed (NC) connections along with the common (COM) terminal. See FIGURE 2

for connection details.

The relay will energize once the ion detection threshold has been exceeded proving ion

output is present. The relay will change state once the unit is detecting. There is a 12 second

delay after ion detection has ceased to prevent cycling.

II. WIRING TO THE GPS-iMOD POWER SUPPLY

1. Remove cable gland. Remove foam filler, but don’t discard. See FIGURE 2.

2. See FIGURE 2 for connections to GPS-iDETECT-P.

3. Remove the red jumper wire between C and NO on the “GPS-iDetect-P” terminal block

  inside the GPS-iMOD power supply (see FIGURE 3 for jumper wire).

4. Use 300V, 18/4, plenum rated, SHIELDED cable wire between the GPS-iDETECT-P terminal

  block and the GPS-iMOD power supply “GPS-iDetect-P” terminal block.

5. Connect the line (L), neutral (N), and common wires (COM or C). See FIGURE 4.

6. Connect the normal open (NO) contact on the GPS-iDETECT-P to the “ON” contact on the

  GPS-iMOD power supply terminal block (see FIGURE 4).

7. Ground 18/4 SHIELD to the ground contact (G) on the “GPS-iDetect-P” terminal (ref.

  FIGURE 4).

•  Only ground ONE end of the shielded cable.

•  Do not ground the end connected to the GPS-iDETECT-P sensor.

•  DO NOT RUN CONTROL WIRING WITH HV CABLES!

8. Pull the cable through the gland. Place foam filler over the cable and then terminate to

  the circuit board. Push the board and foam spacer into the tube. Tighten the cable gland.

9. When the GPS-iDETECT-P senses output, the “Plasma On” light will illuminate on the front

  panel of the power supply and the BAS/BMS Alarm Contacts will close. When using the

  GPS-iDETECT-P in conjunction with the GPS-iMOD power supply, 

always connect to the BMS/BAS using the “BAS Alarm Contacts”  

on the GPS-iMOD power supply, and not directly to the contacts  

on the GPS-iDETECT-P.

!

!

Figure 3

Jumper Wire

Содержание GPS-iDETECT-P

Страница 1: ...www globalplasmasolutions com Installation Operation Maintenance Manual GPS iDETECT P ...

Страница 2: ...rm Contact 24 220VAC 0 5A relay with NO NC and C terminals Dimensions 1 diameter and 10 long Wiring Required 300V 18 4 plenum rated SHIELDED solid strand provided and installed by others LED Status Power On Green LED Detecting Blue LED both are seen from end opposite power entry MECHANCIAL INSTALLATION Mount the GPS iDETECT P to the GPS iMOD bar using the included 1 coated pipe clamp and secure it...

Страница 3: ... present The relay will change state once the unit is detecting There is a 12 second delay after ion detection has ceased to prevent cycling II WIRING TO THE GPS iMOD POWER SUPPLY 1 Remove cable gland Remove foam filler but don t discard See FIGURE 2 2 See FIGURE 2 for connections to GPS iDETECT P 3 Remove the red jumper wire between C and NO on the GPS iDetect P terminal block inside the GPS iMOD...

Страница 4: ... use 18 2 twisted pair SHIELDED plenum rated cable and connect to the BAS Alarm contact terminals inside the GPS iMOD power supply Connect the cable shield to the BAS Alarm ground contact G shown in FIGURE 5 The terminal block may be removed for ease of wiring Keep the control wiring as far from the HV wiring as possible DO NOT RUN BOTH CABLES TOGETHER AND DO NOT ZIP TIE CONTROL WIRING TO FLEXIBLE...

Страница 5: ...asolutions com 3101 Yorkmont Road Suite 400 Charlotte NC 28208 980 279 5622 GPS GPS iDETECT P and its logos are trademarks of Global Plasma Solutions Inc 2020 Global Plasma Solutions Inc 030120 GPSIDETECH P IOM REV A ...

Отзывы: