CONNECTION TO BMS/BAS thru GPS-iMOD Power Supply
Refer to FIGURE 5.
Integral alarm “dry” contacts will close when the system is on and operating properly. To tie
into the BMS/BAS for remote monitoring, use 18/2 twisted pair, SHIELDED, plenum rated cable
and connect to the “BAS Alarm” contact terminals inside the GPS-iMOD power supply.
Connect the cable shield to the “BAS Alarm” ground contact (G) shown in FIGURE 5. The
terminal block may be removed for ease of wiring.
Keep the control wiring as far from the HV wiring as possible.
DO NOT RUN BOTH CABLES TOGETHER AND DO NOT ZIP TIE CONTROL WIRING TO
FLEXIBLE HV CABLES!
!